Figure 3-2 Recommended System Grounding – EK

JOG

LOCAL

PROG

FWD

DISP

 

REV

SHIFT

ENTER

STOP

RESET

 

Note: A boost regulator is required and

Series H

 

 

Note: Wiring shown for clarity of grounding

 

provided with each model EK control.

Note: A line reactor is required and

 

 

method only. Not representative of

 

 

actual terminal block location.

must be ordered separately.

 

L1 L2 L3

T1 T2 T3

 

 

 

 

Note: A load reactor is highly recommended

AC Main

L1

 

 

and must be ordered separately.

 

 

 

Supply

 

Line

Boost

Optional

 

L2

Reactor

Regulator

 

 

 

Load

 

 

 

 

 

 

 

 

Reactor

 

L3

 

 

 

Safety

Earth

 

 

 

Four Wire

 

 

 

Ground

 

 

 

Driven Earth

“Wye”

 

 

 

Route all 4 wires L1, L2, L3 and Earth

 

Ground Rod

 

(Ground) together in conduit or cable.

 

(Plant Ground)

 

 

 

 

Ground per NEC and

 

 

Route all 4 wires T1, T2, T3 and Motor

 

 

Ground together in conduit or cable.

Local codes.

Connect all wires (including motor ground) inside the motor terminal box.

Ungrounded Distribution System

With an ungrounded power distribution system it is possible to have a continuous current path to ground through the MOV devices. To avoid equipment damage, an Isolation transformer with a grounded secondary is recommended. This provides three phase AC power that is symmetrical with respect ground.

Input Power Conditioning

Baldor controls are designed for direct connection to standard three phase lines that are electrically symmetrical with respect to ground. Certain power line conditions must be avoided. An AC line reactor or an isolation transformer may be required for some power conditions.

SBaldor Series H controls require a minimum line impedance of 3%. Refer to “Line Impedance” for additional information.

SIf the feeder or branch circuit that provides power to the control has permanently connected power factor correction capacitors, an input AC line reactor or an isolation transformer must be connected between the power factor correction capacitors and the control.

SIf the feeder or branch circuit that provides power to the control has power factor correction capacitors that are switched on line and off line, the capacitors must not be switched while the control is connected to the AC power line. If the capacitors are switched on line while the control is still connected to the AC power line, additional protection is required. TVSS (Transient Voltage Surge Suppressor) of the proper rating must be installed between the AC line reactor or an isolation transformer and the AC input to the control.

3-6 Receiving & Installation

MN722

Page 17
Image 17
Baldor mn722 manual Ungrounded Distribution System, Input Power Conditioning