Three Phase Input Power Connections
AC power and motor connections are different for controls that have a model number suffix of “EL” and “EK”. Be sure to use the correct procedure for your control.
Note: “EK” Controls are input phase sensitive. Be sure all connections are correct.
“EL” suffix
The AC power and motor connections are shown in Figure
1.Connect the incoming AC power wires from the protection devices to terminals A1, B1 and C1 at the 3% line reactor.
2.Connect A2, B2 and C2 3% line reactor terminals to the L1, L2 and L3 power input terminals of the control.
3.* Connect earth ground to the “ ” of the control. Be sure to comply with local codes.
*Grounding by using conduit or panel connection is not adequate. A separate conductor of the proper size must be used as a ground conductor.
Figure 3-3 “EL” Control 3 Phase AC Power and Motor Connections
| L1 | L2 | L3 |
|
|
| Earth |
Note 1 | * Circuit |
|
|
| Breaker |
|
|
Note 2 |
|
|
|
| A1 | B1 | C1 |
Note 3 | Line |
|
|
Reactor |
|
| |
|
|
| |
| A2 | B2 | C2 |
Note 2 |
|
|
|
| L1 | L2 | L3 |
Baldor
Series 22HXXX-EL
Control
L1 L2 L3
Alternate *
FuseNote 1
Connection
A1 | B1 | C1 |
*Optional components not provided with 22H Control.
Notes:
1.See “Protective Devices” described previously in this section.
2.Shield wires inside a metal conduit.
3.3% Line Reactor is required at input.
See Recommended Tightening Torques in Section 7.
MN722 |