Three Phase Input Power Connections

AC power and motor connections are different for controls that have a model number suffix of “EL” and “EK”. Be sure to use the correct procedure for your control.

Note: “EK” Controls are input phase sensitive. Be sure all connections are correct.

“EL” suffix

The AC power and motor connections are shown in Figure 3-3. Overloads are not required. The 22H control has an electronic I2t motor overload protection. If motor overloads are desired, they should be sized according to the manufacturers specifications and installed between the motor and the T1, T2 and T3 terminals of the control.

1.Connect the incoming AC power wires from the protection devices to terminals A1, B1 and C1 at the 3% line reactor.

2.Connect A2, B2 and C2 3% line reactor terminals to the L1, L2 and L3 power input terminals of the control.

3.* Connect earth ground to the ” of the control. Be sure to comply with local codes.

*Grounding by using conduit or panel connection is not adequate. A separate conductor of the proper size must be used as a ground conductor.

Figure 3-3 “EL” Control 3 Phase AC Power and Motor Connections

 

L1

L2

L3

 

 

 

Earth

Note 1

* Circuit

 

 

 

Breaker

 

 

Note 2

 

 

 

 

A1

B1

C1

Note 3

Line

 

 

Reactor

 

 

 

 

 

 

A2

B2

C2

Note 2

 

 

 

 

L1

L2

L3

Baldor

Series 22HXXX-EL

Control

L1 L2 L3

Alternate *

FuseNote 1

Connection

A1

B1

C1

*Optional components not provided with 22H Control.

Notes:

1.See “Protective Devices” described previously in this section.

2.Shield wires inside a metal conduit.

3.3% Line Reactor is required at input.

See Recommended Tightening Torques in Section 7.