Table 4-4 Inverter Control Board Level 1 Parameter Definitions - Continued

Block Title

Parameter

Description

 

 

 

 

KEYPAD SETUP

Keypad Stop Key

Stop Key - Allows keypad “STOP” key to initiate motor stop during remote or serial

 

 

operation (if Stop key is set to Remote ON). If active, pressing “STOP”

 

 

automatically selects Local mode and initiates the stop command.

 

Keypad Stop Mode

Stop Mode - Selects if the Stop command causes the motor to “COAST” to a stop or

 

 

“REGEN” to a stop. In COAST, the motor is turned off and allowed to

 

 

coast to a stop. In REGEN, the voltage and frequency to the motor is

 

 

reduced at a rate set by “Decel Time”.

 

Keypad Run FWD

Run FWD - ON makes the keypad “FWD” key active in Local mode.

 

Keypad Run REV

Run REV - ON makes the keypad “REV” key active in Local mode.

 

Keypad Jog FWD

Jog FWD - ON makes the keypad “FWD” key active in Local Jog mode.

 

Keypad Jog REV

Jog REV - ON makes the keypad “REV” key active in Local Jog mode.

 

Loc. Hot Start

Loc. Hot Start OFF disables the Stop input at J1-11 in the keypad operating mode.

 

 

ON enables the Stop input at J1-11 in the keypad operating mode.

 

 

 

 

INPUT

Operating Mode

Ten “Operating Modes” are available. Choices are: Keypad, Standard Run, 15SPD, 3

 

 

SPD ANA 2 Wire, 3 SPD ANA 3 Wire, Serial, Bipolar, Process, EPOT 2 Wire and

 

 

EPOT 3 Wire. External connections to the control are made at the J1 terminal strip

 

 

(wiring diagrams are shown in Section 3 “Operating Modes”).

 

Command Select

Selects the external speed reference to be used. The easiest method of speed control is

 

 

to select POTENTIOMETER and connect a 5KW pot to J1-1, J1-2, and J1-3. ± 5, ± 10VDC

 

 

or 4-20mA input command can be applied to J1-4 and J1-5.

 

 

If long distance is required between the external speed control and the control, the 4-20mA

 

 

selections at J1-4 and J1-5 should be considered. Current loop allows long cable lengths

 

 

without attenuation of the command signal.

 

 

10 VOLT W/TORQ FF - when a differential command is present at J1-4 and 5, allows addi-

 

 

tional 5V torque feedforward input at J1-1, 2 and 3 to set a predetermined amount of

 

 

torque inside the rate loop with high gain settings.

 

 

EXB PULSE FOL - selects optional Master Pulse Reference/Isolated Pulse Follower ex-

 

 

pansion board if installed.

 

 

5VOLT EXB - selects optional High Resolution I/O expansion board if installed.

 

 

10VOLT EXB - selects optional High Resolution I/O expansion board if installed.

 

 

4–20mA EXB – selects the 4–20mA input of the optional High Resolution I/O expansion

 

 

board if installed.

 

 

3-15 PSI EXB selects optional 3-15 PSI expansion board if installed.

 

 

Tachometer EXB- selects optional DC Tachometer expansion board if installed.

 

 

Serial -selects optional Serial Communications expansion board if installed.

 

 

None - Used in Process Control mode, two input configuration with no Feedforward input.

 

 

Note: When using the 4-20mA input, the JP1 jumper on the main control board

 

 

must be moved to pins 2 and 3.

 

ANA CMD Inverse

“OFF” will cause a low input voltage (e.g. 0VDC) to be a low motor speed command and

 

 

a maximum input voltage (e.g. 10VDC) to be a maximum motor speed command.

 

 

“ON” will cause a low input voltage (e.g. 0VDC) to be a maximum motor speed command

 

 

and a maximum input voltage (e.g. 10VDC) to be a low motor speed command.

 

ANA CMD Offset

Provides an offset to the Analog Input to minimize signal drift. For example, if the

 

 

minimum speed signal is 1VDC (instead of 0VDC) the ANA CMD Offset can be set to

 

 

-10% so the minimum voltage input is seen by control as 0VDC.

 

ANA 2 Deadband

Allows a defined range of voltage to be a deadband. A command signal within this

 

 

range will not affect the control output. The deadband value is the voltage above and

 

 

below the zero command signal level.

 

ANA 1 CUR Limit

“OFF” Allows normal control operation.

 

 

“ON” Allows the 5V input at J1-2 (referenced to J1-1) to be used for reduction of the

 

 

programmed current limit parameter for torque trimming during operation.

 

 

 

 

 

 

 

 

4-14 Programming & Operation

MN722

Page 61
Image 61
Baldor mn722 manual Keypad Setup, Input