Table 5-3 Converter Section Troubleshooting Continued

INDICATION

POSSIBLE CAUSE

CORRECTIVE ACTION

 

 

 

Over Current FLT

Possible converter transistor failure.

Check transistors for shorted junctions.

 

 

 

 

Incorrect inductance set in Line

Check inductance parameter value.

 

Inductor parameter.

 

 

 

 

Overload FLT

Drive overloaded.

Verify proper sizing of control and motor.

 

 

 

PWR Base FLT

Incorrect phase connections.

Check connections for proper phasing of EK drive components as

 

 

detailed in Section 3 of this manual.

 

 

 

 

Excessive current draw.

Disconnect motor wiring and retry test. If fault remains, call Baldor.

 

 

 

Power device saturated.

 

 

 

 

 

 

Electrical noise from DC coils.

Install flyback diodes (reverse biased 1N4002 or equivalent)across all

 

 

external DC relay coils..

 

 

 

 

Electrical noise from AC coils.

Install RC snubbers on all external AC coils.

 

 

 

Sync To Line

Incorrect phase connections.

Check connections for proper phasing as detailed in Section 3 of this

 

 

manual.

 

 

 

 

Incorrect frequency detected at

Check incoming line voltage and frequency.

 

startup.

 

 

 

 

5-8 Troubleshooting

MN722

Page 77
Image 77
Baldor mn722 manual Converter Section Troubleshooting