Section 1

Quick Start Guide

Overview

If you are an experienced user of Baldor controls, you are probably already familiar with

 

the keypad programming and keypad operation methods. If so, this quick start guide has

 

been prepared for you. This procedure will help get your system up and running in the

 

keypad mode quickly. This will allow motor and control operation to be verified. This

 

procedure assumes that the control and motor are correctly installed (see Section 3 for

 

procedures) and that you have an understanding of the keypad programming & operation

 

procedures. It is not necessary to wire the terminal strip to operate in the keypad mode, if

 

Level 2 Protection block parameters “External Trip” and “Local Enable INP” are set to off.

 

The quick start procedure is as follows:

 

1.

Read the Safety Notice and Precautions in section 2 of this manual.

 

2.

Mount the control. Refer to Section 3, “Physical Location” procedure.

 

3.

Connect AC power. Refer to Section 3, “AC Input Power Connections”.

 

4.

Connect the motor. Refer to Section 3, “Motor Connections”.

 

5.

Connect the encoder. Refer to Section 3, “Encoder Installation”.

Quick Start Checklist

Check of electrical items.

 

CAUTION: After completing the installation but before you apply power, be

 

 

sure to check the following items.

 

1.

Verify AC line voltage at source matches control rating.

 

2.

Inspect all power connections for accuracy, workmanship and torques as well

 

 

as compliance to codes.

 

3.

Verify control and motor are grounded to each other and the control is

 

 

connected to earth ground.

 

4.

Check all signal wiring for accuracy.

 

5.

Be certain all brake coils, contactors and relay coils have noise suppression.

 

 

This should be an R-C filter for AC coils and reverse polarity diodes for DC

 

 

coils. MOV type transient suppression is not adequate.

 

WARNING: Make sure that unexpected operation of the motor shaft during start

 

 

up will not cause injury to personnel or damage to equipment.

 

Check of Motor and Coupling

 

1.

Verify freedom of motion of motor shaft.

 

2.

Verify that motor coupling is tight without backlash.

 

2.

Verify the holding brakes if any, are properly adjusted to fully release and set to

 

 

the desired torque value.

MN722

Quick Start Guide 1-1

Page 6
Image 6
Baldor mn722 manual Overview, Quick Start Checklist, Sure to check the following items, Check of Motor and Coupling