Table A-3 Power Output Parameter Block Values Level 2

Continued

 

 

 

 

 

 

 

 

 

Level 2 Blocks - Continued

 

 

 

 

 

 

 

 

 

Block Title

Parameter

P#

 

Adjustable Range

Factory

User

 

 

 

 

 

 

Setting

 

 

 

 

 

 

 

COMMUNICATIONS

PROTOCOL

2801

 

0-RS-232 ASCII, 1-RS"485 ASCII,

RS–232

 

 

 

 

 

2-RS-232 BBP, 3-RS"485 BBP

BBP

 

 

 

 

 

 

 

 

 

BAUD RATE

2802

 

0-9600, 1-19.2KB, 2-38.4KB, 3-57.6KB,

9600

 

 

 

 

 

4-115.2KB, 5-230.4KB, 6-460.8KB,

 

 

 

 

 

 

7-921.6KB

 

 

 

 

 

 

 

 

 

 

DRIVE ADDRESS

2803

 

0 - 31

0

 

 

 

 

 

 

 

 

AUTO-TUNING

CALC PRESETS

2508

 

0–NO, 1–YES

NO

 

 

 

 

 

 

 

 

 

CMD OFFSET TRM

AU1

 

-

-

 

 

Measures and trims out

 

 

 

 

 

 

offset voltage at Analog

 

 

 

 

 

 

Input #2 (J1-4 & J1-5).

 

 

 

 

 

 

 

 

 

 

 

 

 

CUR LOOP COMP

AU2

 

-

-

 

 

Measures current

 

 

 

 

 

 

response while running

 

 

 

 

 

 

motor at one half the rated

 

 

 

 

 

 

motor current.

 

 

 

 

 

 

 

 

 

 

 

 

 

STATOR R1

AU3

 

-

-

 

 

Measures stator resistance

 

 

 

 

 

 

 

 

 

 

 

 

 

FLUX CUR SETTING

AU4

 

-

-

 

 

Sets the Motor Mag Amps.

 

 

 

 

 

 

 

 

 

 

 

 

 

FEEDBACK TESTS

AU5

 

-

-

 

 

Checks the Master

 

 

 

 

 

 

Encoder and Feedback

 

 

 

 

 

 

Align values.

 

 

 

 

 

 

 

 

 

 

 

 

 

SLIP FREQ TEST

AU6

 

-

-

 

 

Measures motor Slip

 

 

 

 

 

 

Frequency during motor

 

 

 

 

 

 

acceleration/deceleration

 

 

 

 

 

 

at repeated intervals.

 

 

 

 

 

 

 

 

 

 

 

 

 

SPD CNTRLR CALC

AU7

 

 

-

 

 

Measures the motor

 

 

 

 

 

 

current to acceleration

 

 

 

 

 

 

ratio during motor rotation.

 

 

 

 

 

 

This procedure adjusts the

 

 

 

 

 

 

Speed INT Gain and

 

 

 

 

 

 

Speed PROP Gain

 

 

 

 

 

 

parameters.

 

 

 

 

 

 

 

 

 

 

 

 

LEVEL 1 BLOCK

Enters Level 1 Menu - See Table A-2.

 

 

 

 

 

 

 

PRESS ENTER FOR

Exit programming mode and return to display mode.

 

 

PROGRAMMING EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

MN722

Appendix A-7

Page 116
Image 116
Baldor mn722 manual Communications Protocol, BBP Baud Rate, Drive Address, Auto-Tuning, AU1, AU2, AU3, AU4, AU5, AU6, AU7