Section 1
General Information

Programming & Operation 4-9MN722

Program Mode Continued

Initialize New Firmware

After new firmware is installed, the control must be initialized to the new firmware version

and memory locations. Use the following procedure to Initialize the firmware.

Action Description Display Comments
Apply Power Keypad Display shows this
opening message. Logo display for 5 seconds.
If no faults and programmed for
LOCAL operation. Display mode. Stop LED on.
Press PROG key Enter program mode.
Press or key Scroll to Level 2 Blocks.
Press ENTER key Select Level 2 Blocks.
Press or key Scroll to the Miscellaneous block.
Press ENTER key Select Miscellaneous block.
Press key Scroll to Factory Settings
parameter.
Press ENTER key Access Factory Settings
parameter. represents blinking cursor.
Press key Scroll to YES, to choose original
factory settings.
Press ENTER key Restores factory settings. Loading Presets is first message
Operation Done is next
No is displayed last.
Press key Scroll to menu exit.
Press ENTER key Return to display mode. Display mode. Stop LED on.
Press DISP key several
times Scroll to diagnostic information
screen. If you wish to verify the software
version, enter diagnostic info.
Press ENTER key Access diagnostic information. Displays commanded speed,
direction of rotation, Local/
Remote and motor speed.
Press DISP key Display mode showing software
version and revision installed in
the control.
Verify new firmware version.
Press DISP key Displays exit choice. Press ENTER to exit diagnostic
information.