Figure 3-2 Configuring the Control Transformer for 380 - 400 VAC Installation

Contactor Transformer

Only size E and F controls require a change of the contactor transformer tap.

See Figure 3-3. Use the taps (H1 to H5) that are correct for the input voltage.

Figure 3-3 Contactor Transformer Tap Change (380 -400VAC Input)

 

 

 

 

 

 

 

 

H5

Frequency

 

Voltage

 

Taps

 

 

 

 

 

600VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H4

 

 

 

 

 

 

 

 

 

 

 

 

 

50 / 60

 

380

 

H1 – H2

 

 

 

550VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hz

 

440-460

 

H1 – H3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H3

 

 

 

550

 

H1 – H4

 

 

 

 

 

 

600

 

H1 – H5

 

440VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H1H2

380VAC

Size G+and H control procedure: (Refer to Figure 3-4.)

Control Transformer

1.Be sure drive operation is terminated and control is disabled.

2.Remove all power sources from the control. If power has been applied, wait at least 5 minutes for bus capacitors to discharge.

3.Remove or open the front cover. Locate the control transformer fuse block (see Figure 3-1).

4.Remove the wires from the two right side terminals (460VAC connection).

5.Place the wires on the center terminals as shown (380VAC connection).

6.Install or close the front cover.

Figure 3-4 Configuring the Control Transformer Fuse Block for 380 - 400 VAC Installation

For Fuse Block, location refer to Figure 3-1.

460VAC

380-400VAC

Connection

Connection

3-14 Receiving & Installation

MN722

Page 25
Image 25
Baldor mn722 manual Contactor Transformer Tap Change 380 -400VAC Input, Size G+and H control procedure Refer to Figure