Table 4-5 Inverter Control Board Level 2 Parameter Definitions

Block Title

Parameter

Description

 

 

 

OUTPUT LIMITS

Operating Zone

Sets the PWM operating zone to Standard 2.5KHz or Quiet 8.0KHz output carrier

 

 

frequency. Two operating modes are also selectable: Constant Torque and Variable

 

 

Torque.

 

 

Constant Torque allows 170 - 200% for 3 seconds overload or 150% for 60 seconds

 

 

overload.

 

 

Variable Torque allows 115% peak overload for 60 seconds.

 

MIN Output Speed

Sets the minimum motor speed in RPM. During operation, the motor speed will not be

 

 

allowed to go below this value except for motor starts from 0 RPM or during dynamic

 

 

braking to a stop.

 

MAX Output Speed

Sets the maximum motor speed in RPM.

 

PK Current Limit

The maximum output peak current to the motor. Values above 100% of the rated current

 

 

are available depending upon the operating zone selected.

 

PWM Frequency

The frequency that the output transistors are switched. PWM frequency is also referred

 

 

to as “Carrier” frequency. PWM should be as low as possible to minimize stress on

 

 

the output transistors and motor windings. It is recommended that the PWM

 

 

frequency be set to approximately 15 times the maximum output frequency of the

 

 

control. Ratios less than 15 will result in non-Sinusoidal current waveforms. See

 

 

Figure 4-3.

 

CUR Rate Limit

Limits the rate of torque change in response to a torque command.

 

 

 

CUSTOM UNITS

Decimal Places

The number of decimal places of the Output Rate display on the Keypad display. This

 

 

value will be automatically reduced for large values. The output rate display is only

 

 

available if the Value At Speed parameter value is non zero.

 

Value At Speed

Sets the desired output rate per RPM of motor speed. Two numbers are displayed on

 

 

the keypad display (separated by a slash “/”). The first number (left most) is the value

 

 

you want the keypad to display at a specific motor speed. The second number (right

 

 

most) is the motor RPM corresponding to the units in the first number. A decimal may

 

 

be inserted into the left numbers by placing the flashing cursor over the up/down

 

 

arrow and use the arrow keys.

 

Units of Measure

Allows user specified units of measure to be displayed on the Output Rate display. Use

 

 

the shift and arrow keys to scroll to the first and successive characters. If the

 

 

character you want is not displayed, move the flashing cursor over the special

 

 

up/down character arrow on the left side of the display. Use the up/down arrows and

 

 

the shift key to scroll through all 9 character sets. Use the ENTER key to save your

 

 

selection.

 

 

 

PROTECTION

Overload

Sets the protection mode to Fault (trip off during overload condition) or to Foldback

 

 

(automatically reduce the output current below the continuous output level) during an

 

 

overload. Foldback is the choice if continuous operation is desired. Fault will require

 

 

the control be “Reset” manually or automatically after an overload.

 

 

Note: The “Foldback” selection may not be available on some early versions of

 

 

the software.

 

External Trip

OFF - External Trip is Disabled.

 

 

ON - External Trip is enabled. If a normally closed contact at J1-16 is opened, an

 

 

External Trip fault will occur and cause the drive to shut down.

 

 

 

Local Enable INP

Following Error

Torque Proving

OFF - Ignores J1-8 input when in the “LOCAL” mode.

ON - Requires J1-8 input to be closed to enable the control when in the “LOCAL” mode.

This parameter determines if the control is to monitor the amount of following error that occurs in an application. Following Error is the programmable tolerance for the AT Speed Opto output as defined by the Level 1 Output block, AT Speed Band parameter. Operation outside the speed range will cause a fault and the drive will shut down.

When this parameter is set to ON the control measures output current in all three phases to the motor. If output current is unbalanced, the control will trip off generating a torque proving fault. In a hoist application, for example, this is useful to ensure that motor torque exists before the fail safe brake is released. “Drive On” output, if programmed, will not occur if torque proving fails.

4-18 Programming & Operation

MN722

Page 65
Image 65
Baldor mn722 manual Inverter Control Board Level 2 Parameter Definitions, Output Limits, Custom Units, Protection