| Table |
|
|
FAULT MESSAGE | DESCRIPTION |
|
|
Current Sens FLT | Defective phase current sensor or open circuit detected between control board and current |
| sensor. |
DC Bus High | Bus over voltage condition occurred. |
DC Bus Low | Bus under voltage condition occurred. |
GND FLT | Low impedance path detected between an output phase and ground. |
High INIT CUR | Phasing between main power connections, zero crossing detectors, line reactor and |
| control does not match. |
ID:No Feedback | Control board installed in power base that does not have current feedback and current |
| feedback is required. |
INT | Temperature of control heatsink exceeded safe level. |
Invalid Base ID | Control does not recognize power base ID. |
Logic Supply FLT | Logic power supply not working properly. |
Lost AB Phase | Missing phase detected by mP. |
Lost BC Phase | Missing phase detected by mP. |
Lost User Data | Battery backed RAM parameters have been lost or corrupted. |
| When fault cleared (Reset), the control should reset to factory preset values. |
Low INIT Bus V | Insufficient bus voltage on startup. |
Memory Error | EEPROM error occurred. Contact Baldor. |
mP Reset | Watchdog timer detected error. |
New Base ID | Control board sensed a different power base since last time it was powered up. |
No Faults | Fault log is empty. |
Overcurrent FLT | Instantaneous over current condition detected by bus current sensor. |
Overload | Output current exceeded allowable rating. |
PWR Base FLT | Desaturation of power device occurred or bus current threshold exceeded. |
Sync To Line | Incorrect line phasing or frequency detected on startup. |
|
|
MN722 |