Table 5-1 Converter Control Board Fault Messages

 

 

FAULT MESSAGE

DESCRIPTION

 

 

Current Sens FLT

Defective phase current sensor or open circuit detected between control board and current

 

sensor.

DC Bus High

Bus over voltage condition occurred.

DC Bus Low

Bus under voltage condition occurred.

GND FLT

Low impedance path detected between an output phase and ground.

High INIT CUR

Phasing between main power connections, zero crossing detectors, line reactor and

 

control does not match.

ID:No Feedback

Control board installed in power base that does not have current feedback and current

 

feedback is required.

INT Over-Temp

Temperature of control heatsink exceeded safe level.

Invalid Base ID

Control does not recognize power base ID.

Logic Supply FLT

Logic power supply not working properly.

Lost AB Phase

Missing phase detected by mP.

Lost BC Phase

Missing phase detected by mP.

Lost User Data

Battery backed RAM parameters have been lost or corrupted.

 

When fault cleared (Reset), the control should reset to factory preset values.

Low INIT Bus V

Insufficient bus voltage on startup.

Memory Error

EEPROM error occurred. Contact Baldor.

mP Reset

Watchdog timer detected error.

New Base ID

Control board sensed a different power base since last time it was powered up.

No Faults

Fault log is empty.

Overcurrent FLT

Instantaneous over current condition detected by bus current sensor.

Overload

Output current exceeded allowable rating.

PWR Base FLT

Desaturation of power device occurred or bus current threshold exceeded.

Sync To Line

Incorrect line phasing or frequency detected on startup.

 

 

5-2 Troubleshooting

MN722

Page 71
Image 71