Wire Size and Protection Devices
Table 3-5 230VAC Controls (3 Phase) Wire Size and Protection Devices
Control Rating | Input Breaker | Input Fuse (Amps) | Wire Gauge | |||
Amps | HP | (Amps) | Fast Acting | Time Delay | AWG | mm2 |
3 | 0.75 | 7 | 5 | 4 | 14 | 2.5 |
4 | 1 | 7 | 6 | 5 | 14 | 2.5 |
7 | 2 | 15 | 12 | 9 | 14 | 2.5 |
10 | 3 | 15 | 15 | 12 | 14 | 2.5 |
16 | 5 | 20 | 25 | 20 | 12 | 3.31 |
22 | 7.5 | 30 | 35 | 30 | 10 | 5.26 |
28 | 10 | 40 | 45 | 35 | 8 | 8.37 |
42 | 15 | 60 | 70 | 60 | 6 | 13.3 |
54 | 20 | 70 | 80 | 70 | 6 | 13.3 |
68 | 25 | 90 | 100 | 90 | 4 | 21.2 |
80 | 30 | 100 | 125 | 110 | 3 | 26.7 |
104 | 40 | 150 | 175 | 150 | 1 | 42.4 |
130 | 50 | 175 | 200 | 175 | 1/0 | 53.5 |
145 | 60 | 200 | 225 | 200 | 2/0 | 67.4 |
192 | 75 | 250 | 300 | 250 | 4/0 | 107.0 |
Table 3-6 460VAC Controls (3 Phase) Wire Size and Protection Devices
Control Rating | Input Breaker | Input Fuse (Amps) | Wire Gauge | |||
|
| (Amps) |
|
|
|
|
Amps | HP | Fast Acting | Time Delay | AWG | mm2 | |
2 | 0.75 | 3 | 2 | 2 | 14 | 2.5 |
2 | 1 | 3 | 3 | 2.5 | 14 | 2.5 |
4 | 2 | 7 | 5 | 4.5 | 14 | 2.5 |
5 | 3 | 7 | 8 | 6.3 | 14 | 2.5 |
8 | 5 | 15 | 12 | 10 | 14 | 2.5 |
11 | 7.5 | 15 | 17.5 | 15 | 14 | 2.5 |
14 | 10 | 20 | 20 | 17.5 | 12 | 3.31 |
21 | 15 | 30 | 30 | 25 | 10 | 5.26 |
27 | 20 | 40 | 40 | 35 | 10 | 5.26 |
34 | 25 | 50 | 50 | 45 | 8 | 8.37 |
40 | 30 | 50 | 60 | 50 | 8 | 8.37 |
52 | 40 | 70 | 80 | 70 | 6 | 13.3 |
65 | 50 | 90 | 100 | 90 | 4 | 21.2 |
77 | 60 | 100 | 125 | 100 | 3 | 26.7 |
96 | 75 | 125 | 150 | 125 | 2 | 33.6 |
124 | 100 | 175 | 200 | 175 | 1/0 | 53.5 |
156 | 125 | 200 | 250 | 200 | 2/0 | 67.4 |
180 | 150 | 225 | 300 | 250 | 3/0 | 85.0 |
240 | 200 | 300 | 350 | 300 | (2) 2/0 | (2) 67.4 |
302 | 250 | 400 | 450 | 400 | (2) 4/0 | (2) 107.0 |
361 | 300 | 450 | 600 | 450 | (3) 2/0 | (3) 67.4 |
414 | 350 | 500 | 650 | 500 | (3) 3/0 | (3) 85.0 |
477 | 400 | 600 | 750 | 600 | (3) 4/0 | (3) 107.0 |
515 | 450 | 650 | 800 | 700 | (3) 250MCM | (3) 127.0 |
590 | 500 | 750 | 900 | 800 | (3) 300MCM | (3) 152.0 |
Note: All wire sizes are based on 75° C copper wire. Higher temperature smaller gauge wire may be used per NEC and local codes. Recommended fuses/breakers are based on 40° C ambient, maximum continuous control output current and no harmonic current.
MN722 | Receiving & Installation |