Table 1-13. Server Module Messages (continued)
Message | Causes | Corrective Actions |
|
|
|
Error: Memory failure | Faulty or improperly seated memory | See "Troubleshooting Server Module |
detected. Memory size | modules. | Memory" on page 112. |
reduced. Replace the |
|
|
faulty DIMM as soon as |
|
|
possible. |
|
|
|
|
|
Error: Remote Access | Faulty or improperly installed | Reinstall the DRAC/MC module. See |
Controller initialization | DRAC/MC module. | "DRAC/MC Module" on page 26. |
failure. |
| If the problem persists, replace the |
|
| |
|
| DRAC/MC module. |
FBD training error: The following branch has been disabled: Branch x.
The specified branch (channel pair) contains DIMMs that are incompatible with each other.
Ensure that only Dell qualified memory is used. Dell recommends purchasing memory upgrade kits directly from http://www.dell.com or your Dell sales agent to ensure compatibility.
Gate A20 failure | Faulty keyboard controller (faulty | See "Getting Help" on page 127. | |
| server module board). |
| |
|
|
| |
General failure | Operating system corrupted or | Reinstall the operating system. | |
| improperly installed. |
| |
|
|
| |
Keyboard controller | Faulty keyboard controller (faulty | See "Getting Help" on page 127. | |
failure | server module board). |
| |
|
|
| |
Keyboard data line failure | Loose or improperly connected | Ensure that the keyboard is properly | |
Keyboard failure | keyboard cable; faulty keyboard to the | connected. If the problem persists, | |
custom cable; faulty keyboard | replace the keyboard. | ||
Keyboard stuck key failure | |||
controller. | If the message still appears, the keyboard | ||
|
| ||
|
| controller is faulty. See "Getting Help" | |
|
| on page 127. | |
|
|
| |
Manufacturing mode | System is incorrectly configured. | Set the NVRAM_CLR switch to "on" | |
detected |
| and reboot the server module. See | |
|
| Figure |
About Your System
37