2-3-3 Connecting the control terminals

Table 2-3-3 lists the functions of the control circuit terminals. A control circuit terminal should be connected according to the setting of its functions.

Table 2-3-3

Classification

Terminal

Terminal name

 

 

 

Function

 

 

 

 

 

 

symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

Potentiometer power

 

Used for +10V DC power supply for frequency setting POT (variable

 

 

supply

 

resistor of 1 to 5kΩ)

 

 

 

 

 

 

 

12

Voltage input

 

Frequency is set according to the analog input voltage supplied from

 

 

 

 

 

an external circuit.

 

 

 

 

 

 

 

 

 

 

 

- 0 to +10V DC/0 to 100%

 

 

 

 

 

 

 

 

 

 

 

- Reversible operation using positive and negative signals:0 to +/-

 

 

 

 

 

10V DC/0 to 100%

 

 

 

 

 

 

 

 

 

 

 

- Reverse operation: +10 to 0V DC/0 to 100%

 

 

 

 

 

 

 

 

The feedback signal for PID control is input.

 

 

 

 

 

 

 

 

The analog input value from the external circuit is used for torque

 

 

 

 

 

control. (P11S does not support this function.)

 

 

 

 

 

 

 

*

Input resistance: 22kΩ

 

 

 

 

 

 

 

V2

Voltage input

Frequency is set according to the analog input voltage supplied from an

Analog input

 

 

 

external circuit

 

 

 

 

 

 

 

 

 

 

- 0 to +10V DC/0 to 100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Reverse operation:+10 to 0V DC/0 to 100%

 

 

 

 

 

 

 

 

* It can be used only one terminal "V2" or "C1" alternatively

 

 

 

 

 

*

Input resistance:22kΩ

 

 

 

 

 

 

 

C1

Current input

 

Frequency is set according to the analog input current supplied from

 

 

 

 

 

an external circuit.

 

 

 

 

 

 

 

 

 

 

 

- 4 to 20mA DC/0 to 100%

 

 

 

 

 

 

 

 

 

 

 

- Reverse operation:20 to 4mA DC/0 to 100%

 

 

 

 

 

 

 

 

The feedback signal for PID control is input.

 

 

 

 

 

 

 

 

PTC thermistor input

 

 

 

 

 

 

 

 

 

 

* It can be used only one terminal "V2" or "C1" alternatively.

 

 

 

 

 

*

Input resistance:250Ω

 

 

 

 

 

 

 

11

Analog input common

Common terminal for analog input signals

 

 

 

 

 

 

 

FWD

Forward operation/stop

 

Used for forward operation (when FWD-CM is on) or deceleration and

 

 

command

 

stop (when FWD-CM is off)

 

 

 

 

 

 

 

REV

Reverse operation/stop

 

Used for reverse operation (when REV-CM is on) or deceleration and

 

 

command

 

stop (when REV-CM is off)

 

 

 

 

 

 

 

X1

Digital input 1

 

The coast-to-stop command, external alarm, alarm reset, multistep

 

X2

Digital input 2

 

frequency selection, and other functions (from an external circuit) can be

 

X3

Digital input 3

 

assigned to terminals X1 to X9. For details, see "Setting the Terminal

 

 

Functions E01 to E09" in Section 5.2, "Details of Each Function."

 

X4

Digital input 4

 

 

 

<Specifications of digital input circuit>

 

 

 

 

 

 

 

X5

Digital input 5

 

 

 

 

 

 

 

 

*

 

 

 

 

 

 

 

 

 

X6

Digital input 6

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

min.

 

typ.

 

max.

 

X7

Digital input 7

 

 

Operating voltage

ON level

2V

 

-

 

2V

 

 

 

 

 

 

 

OFF level

22V

 

24V

 

27V

 

 

X8

Digital input 8

 

 

Digital input

 

 

Operating current at ON level

-

 

3.2mA

 

4.5mA

 

X9

Digital input 9

 

 

 

 

 

 

 

Allowable leakage current at OFF level

-

 

-

 

0.5mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CM

Common terminal

Common terminal for Digital input and FMP terminals

 

 

 

 

 

P24

Control Unit power Supply

+24VDC power supply for control input. Maximum output current 100mA

 

PLC

PLC signal power

Used to connect power supply for PLC output signals (rated voltage

 

 

 

 

24(22 to 27) V DC) at source logic operation.

 

 

 

 

 

FMA

Analog monitor

Outputs monitor signal using analog DC voltage 0 to +10V DC.

 

 

 

(11:

 

 

The meaning of this signal is one of the following:

 

 

 

 

 

Common

 

 

-Output frequency (before slip compensation) -Power consumption

 

terminal)

 

 

-Output frequency (after slip compensation) -PID feedback value

Analog output

 

 

 

-Output current -PG feedback value

 

 

 

 

 

 

 

 

 

 

-Output voltage -DC link circuit voltage

 

 

 

 

 

 

 

 

 

 

-Output torque -Universal AO

 

 

 

 

 

 

 

 

 

 

-Load factor

 

 

 

 

 

 

 

 

 

 

*Connectable impedance:5kΩ minimum

 

 

 

 

 

 

2-13