F35

FMP terminal (function)

Monitor data (e.g.,output frequency, output current) can be output to terminal FMP as pulse voltage. Monitor data can also be sent to an analog meter as average voltage.

When sending data to a digital counter or other instrument as pulse output, set the pulse rate in F33 to any value and the voltage in F34 to 0%.

When data is sent to an analog meter or other instrument as average voltage, the voltage value set in F34 determines the average voltage and the pulse rate in F33 is fixed to 2670 (p/s).

‹This function sets the pulse frequency of the monitor item selected in F35 within a range of 300 to 6000 (p/s) in 1 p/s steps.

F

3

3

F

M

P

 

P

U

L

S

E

S

Setting range: 300 to 6,000 p/s

T1

About 15.6V

0V

VL:0.5VMAX

T

Pulse cycle time

Pulse frequency (p/s) = 1/T

Duty (%) = T1/T x 100

Average voltage (V) = 15.6 x T1/T

The output terminal of the FMP terminal is composed of the transistor, therefore there is a saturation voltage (0.5VMAX). When using in the analogue by the filter processing the pulse voltage, it should be make a 0V adjustment by external equipment.

‹This function sets the average voltage of pulse output to terminal FMP.

F

3

4

F

M

P

 

V

-

A

D

J

 

 

 

Setting range

0%: The pulse rate varies depending on the monitor amount of the monitor item selected in F35. (The maximum value is the value set in F33. The pulse duty is fixed at 50%.)

1 to 200%: Pulse rate is fixed at 2,670 p/s. The average voltage of the monitor item selected in F35 when the monitor amount is 100% is adjusted in the 1 to 200% range (1% steps).

(The pulse duty varies.)

F36

30Ry operation mode

‹This function specifies whether to activate (excite) the alarm output relay (30Ry) for any fault at normal or alarm status.

 

F

3

6

3

0

R

Y

 

 

M

O

D

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set

 

 

 

 

 

 

 

Operation

 

value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

At normal

30A

- 30C: OFF, 30B - 30C: ON

 

At abnormal 30A

- 30C: ON, 30B - 30C:OFF

 

 

 

 

1

 

At normal

30A

- 30C:ON, 30B - 30C: OFF

 

At abnormal 30A

- 30C: OFF, 30B - 30C: ON

 

 

 

 

‹When the set value is 1, contacts 30A and 30C are connected when the inverter control voltage is established (about one second after power on).

‹When the power is off, contacts 30A and 30C are OFF; 30B and 30C are ON.

30A

30

 

30B

30C

F40

Torque limiter 1

(driving)

F41

Torque limiter 1

(braking)

‹The torque limit operation calculates motor torque from the output voltage, current and the primary resistance value of the motor, and controls the frequency so the calculated value does not exceed the limit. This operation enables the inverter to continue operation under the limit even if a sudden change in load torque occurs.

‹Select limit values for the driving torque and braking torque.

‹When this function is activated, acceleration and deceleration operation times are longer than the set values.

‹The motor tuning (P04 / A13) should be set to "2" for this function is valid.

‹The increase frequency upper bound during torque limit operation is set by function code : U01.

‹When the setting value is selected "0" (prevent OU trip), the operation mode is selected by function code : U60. The details are referred to the functions : U01, U60.

Related functions:

U01, U60

F

4

0

D

R

V

 

T

R

Q

1

 

 

F

4

1

B

R

K

 

T

R

Q

1

 

 

‹This function selects the monitor item to be output to terminal FMP.

F

3

5

F

M

P

 

F

U

N

C

 

 

 

 

 

The set value and monitor items are the same as those of F31.

Function

Torque

limit

(driving)

Torque

limit

(braking)

Setting range

G11S:20% to 200% P11S:20% to 150%

999

G11S:20% to 200% P11S:20% to 150%

0

999

Operation

The torque is limited to the set value.

Torque limiting inactive

The torque is limited to the set value.

Prevents OU trip due to power regeneration effect automatically.

Torque limiting inactive

5-16