E33

OL function signal (mode select)

‹Select one of the following two types of overload early warning: early warning by electronic thermal O/L relay function or early warning by output current.

 

E

3

3

O

L

 

 

W

A

R

N

I

N

G

 

 

Set

value 0: Electronic thermal O/L relay

 

 

 

 

 

1: Output current

Set

Function

 

 

 

 

 

Description

value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

Electronic

 

Overload early warning by electronic

 

 

thermal

 

thermal O/L relay (having inverse-time

 

 

O/L relay

 

characteristics) to output current.

 

 

 

 

 

 

 

The operation selection and thermal

 

 

 

 

 

 

 

time constant for the inverse-time

 

 

 

 

 

 

 

characteristics are the same as those

 

 

 

 

 

 

 

of the electronic thermal O/L relay for

 

 

 

 

 

 

 

motor protection (F10 and F12).

1

Output

 

An overload early warning is issued

 

 

current

 

when output current exceeds the set

 

 

 

 

 

 

 

current value for the set time.

 

 

 

 

 

 

 

The figure of OL2(E37) is refferred.

‹This function cannot be used when Motor 2 is selected.

E34

OL function signal (Level)

‹This function determines the operation level of the electronic thermal O/L relay or output current.

E

3

4

O

L

1

 

L

E

V

E

L

 

 

 

Setting range G11S:Inverter rated output current x (5 to 200%) P11S:Inverter rated output current x (5 to 150%)

The operation release level is 90% of the set value.

‹This function cannot be used when Motor 2 is selected.

E35

 

 

 

OL function signal (Timer)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

3

5

O

L

1

 

T

I

M

E

R

 

‹This function is used when 1 (output current) is set to "E33 Overload early warning (operation selection)." Setting range: 0.1 to 60.0 seconds

‹Set the time from when the operation level is attained until the overload early warning function is activated.

E36

FDT2 function (Level)

‹This function determines the operation (detection) level of output frequency for “2nd Freq. level detection [FDT2]”. The hysteresis width for operation release is set by the function E32: FDT1 function signal (Hysteresis).

E 3 6 F D T 2 L E V E L

Setting range(Operation level) : G11S: 0 to 400 Hz P11S: 0 to 120 Hz

E37

OL2 function (Level)

‹This function determines the operation level of the output current for “2nd OL level detection [OL2]”.

E

3

7

O

L

2

 

L

E

V

E

L

 

 

 

Setting range G11S:Inverter rated output current x (5 to 200%) P11S:Inverter rated output current x (5 to 150%)

The operation release level is 90% of the set value.

Output current

E37 OL2 LEVEL

 

(E34 OL1 LEVEL)

OL2 LEVEL x 90%

 

(OL1 LEVEL x 90%)

 

E35

 

OL TIMER

[OL2]

O N

E40

Display coefficient A

E41

Display coefficient B

‹These coefficients are conversion coefficients which are used to determine the load and line speed and the target value and feedback amount (process amount) of the PID controller displayed on the LED monitor.

E

4

0

C

O

E

F

 

A

 

 

 

 

E

4

1

C

O

E

F

 

B

 

 

 

 

Setting range

Display coefficient A:-999.00 to 0.00 to +999.00

Display coefficient B:-999.00 to 0.00 to +999.00

‹Load and line speed

Use the display coefficient A.

Displayed value = output frequency x (0.01 to 200.00) Although the setting range is ±999.00, the effective value range of display data is 0.01 to 200.00. Therefore, values smaller or larger than this range are limited to a minimum value of 0.01 or a maximum value of 200.00.

‹Target value and feedback amount of PID controller Set the maximum value of display data in E40, "Display coefficient A," and the minimum value in E41, "Display coefficient B."

Displayed value = (target value or feedback amount) x (display coefficient A - B)+B

Displayed value

A

 

B

Target value or

 

feedback amount

0%

100%

5-26