Fuji Bikes 5000G11S/P11S instruction manual C33 Analog setting signal filter, T E R

Models: 5000G11S/P11S

1 132
Download 132 pages 56.51 Kb
Page 78
Image 78

C33

Analog setting signal filter

‹Analog signals input from control terminal 12 or C1 may contain noise, which renders control unstable. This function adjusts the time constant of the input filter to remove the effects of noise.

C 3 3 R E F

F

I L T E R

Setting range: 0.00 to 5.00 seconds

‹An set value too large delays control response though stabilizing control. A set value too small speeds up control response but renders control unstable.

If the optimum value is not known, change the setting when control is unstable or response is delayed.

Note:

The set value is commonly applied to terminals 12 and C1. For input of PID feedback amount, the PID control feedback filter (set in H25) is used.