Fuji Bikes 5000G11S/P11S instruction manual Motor selected Related function

Models: 5000G11S/P11S

1 132
Download 132 pages 56.51 Kb
Page 66
Image 66
Operation selected
No DC injection brake command is given. A DC injection brake command is given.

Coast-to-stop command [BX]

When BX and P24 are connected, inverter output is cut off immediately and the motor starts to coast-to-stop. An alarm signal is neither output nor self-held. If BX and P24 are disconnected when the operation command (FWD or REV) is on, operation starts at the start frequency. To use this BX terminal function, assign value "7" to the target digital input terminal.

Output

Forward

 

Forward

Forward

rotation

Ignored

rotation

rotation

Frequency

 

 

 

 

 

 

 

FWD

ON

ON

REV

 

ON

 

 

BX

 

 

ON

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

Alarm reset [RST]

When an inverter trip occurs, connecting RST and P24 clears the alarm output (for any fault) ; disconnecting them clears trip indication and restarts operation. To use this RST terminal function, assign value "8" to the target digital input terminal.

External fault [THR]

Disconnecting THR and P24 during operation cuts off inverter output (i.e., motor starts to coast-to-stop) and outputs alarm OH2, which is self-held internally and cleared by RST input. This function is used to protect an external brake resistor and other components from overheating. To use this THR terminal function, assign value "9" to the target digital input terminal. ON input is assumed when this terminal function is not set.

Jogging operation[JOG]

This function is used for jogging (inching) operation to position a work piece. When JOG and P24 are connected, the operation is performed with the jogging frequency set in function code C20 while the operation command (FWD-P24 or REV-P24) is on. To use this JOG terminal function, assign value "10" to the target digital input terminal.

Note: It is possible to change to the JOG operation by keypad panel when keypad panel operation.

JOG

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

OFF

 

 

ON

 

Input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

 

 

 

 

 

 

 

 

 

 

 

OFF

ON

OFF

ON

OFF

ON

OFF

ON

 

command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(FWD/REV)

STOP

RUN

STOP

RUN

STOP

RUN

STOP

RUN

 

Operation

 

 

 

 

 

 

 

 

 

 

 

 

JOG

 

JOG

 

NOR.

 

NOR.

 

mode

 

OPR.

 

OPR.

 

OPR.

 

OPR.

 

WARNING

-When the JOG command and operation command (FWD/REV) are input at the same time, it can NOT be changed to the JOG operation. It operates with setting frequency.

-When the JOG operation is used, it should be input the operation command after input the JOG command during the inverter is STOP.

-When the JOG command and operation command are input at the same time, the JOG command is assigned to the "Multistep frequency selection (SS1 to SS8)" and used it.

-The inverter can NOT be stopped and JOG operation is continued even JOG command is OFF during JOG operation. The inverter is deceleration to a stop if the operation command is OFF.

Accident may result.

Frequency setting 2/frequency setting 1 [Hz1/Hz2]

This function switches the frequency setting method set in function codes F01 and C30 by an external digital input signal.

Set value input signal

Frequency setting method selected

11

 

 

F01 FREQ CMD1

off

 

 

C30 FREQ CMD2

 

 

 

Note: It can not be used with set value "35" simultaneously. When the set value "11" and "35" are selected, "Er6" is displayed.

Motor 2/motor 1 [M1/M2]

This function switches motor constants using an external digital input signal.

This input is effective only when the operation command to the inverter is off and operation has stopped and does not apply to the operation at 0Hz.

Set value input signal

Motor selected

Related function

 

 

12

A01A18

 

 

 

 

 

 

off

 

Motor 1

 

 

 

Motor 2

DC brake command [DCBRK]

When the external digital input signal is on, DC injection braking starts when the inverter's output frequency drops below the frequency preset in function code F20 after the operation command goes off. (The operation command goes off when the STOP key is pressed at keypad panel operation and when both terminals FWD and REV go on or off at terminal block operation.) The DC injection braking continues while the digital input signal is on. In this case, the longer time of the following is selected:

-The time set in function code F22.

-The time which the input signal is set on.

Set value input signal

13

off

5-19

Page 66
Image 66
Fuji Bikes 5000G11S/P11S instruction manual Motor selected Related function