7-2 Abnormal motor rotation

 

 

 

 

 

 

 

 

(1) If motor does not rotate

 

 

 

 

 

 

 

 

 

 

 

 

Charge lamp (CRG)

NO

Are the circuit breaker and

NO

 

Motor does not rotate.

 

lights and LCD monitor

magnetic contactor on the

Turn on.

 

 

 

 

 

 

 

lights up?

 

 

power supply side switched on?

 

 

 

 

 

YES

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check for problems

Remove the cause of

 

Is the LCD monitor

 

Are the voltages

 

NO

(low voltage,

alarm function activation

YES

 

 

an open-phase,

and reset the alarm,

 

displaying an alarm

 

on the power terminals

 

a loose connection,

 

mode screen?

 

 

(R/L1, S/L2, T/L3) normal?

 

then run the motor.

 

 

 

 

 

poor contact) and

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

YES

 

 

remedy accordingly.

 

 

 

Is operation method

 

Is a jumper or DC reactor

 

 

 

 

 

 

the keypad panel or

 

NO

 

 

 

 

 

 

connected between

 

Connect.

 

 

 

control terminal input?

 

 

 

 

 

 

 

terminals P1 and P(+)?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Keypad

Control

 

YES

 

 

 

 

 

 

panel

 

 

 

 

 

If no error is detected,

terminals

 

 

 

Inverter may be faulty.

 

 

 

 

 

continue operation.

 

 

 

 

 

 

 

Contact Fuji Electric.

YES

 

 

 

 

Are external wiring between

 

 

 

Does the motor run

 

Was the forward or

 

 

 

 

NO

NO

control

circuit

terminals

YES

 

Replace the faulty

if FWD or REV is

reverse operation

 

 

 

 

 

FWD,

REV-CM

connected

 

 

switch or relay.

pressed?

 

 

command given?

 

 

 

 

 

 

 

 

correctly?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

YES

YES

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the

 

 

 

 

 

 

 

 

 

 

key and set

 

NO

Has the frequency

NO

Is the external wiring

 

 

 

the frequency.

Correct the wiring error.

 

been set?

 

 

between control terminals

 

 

 

 

 

 

 

 

 

 

 

YES

YES

 

13, 12, 11, C1and V2 or

NO

 

 

YES

 

 

between X1-X9 and

 

 

 

 

 

 

 

 

 

Does the motor start

 

 

 

 

CM for the multistep

 

 

 

 

 

 

 

frequency selection

 

 

 

when the

key

 

 

 

 

 

 

 

 

 

 

 

connected correctly?

 

 

 

is pressed?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

Are the frequency limiter

 

 

YES

 

Replace the faulty

 

 

 

(High) and the frequency

 

 

 

 

 

 

YES

setting lower than

 

 

 

 

 

frequency setting POT (VR),

 

 

 

the starting frequency?

 

 

 

 

signal converter, switch,

 

 

 

NO

 

 

 

 

 

or relay contacts as required.

Set the frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

correctly.

 

Are the inverter output

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

terminals (U,V,W) provided

Inverter may be faulty.

 

 

 

 

 

 

 

 

 

 

 

with the proper voltage?

 

Contact Fuji Electric.

 

 

 

Faulty motor

 

YES

 

 

 

 

 

 

 

 

NO

 

Are the cables to

 

 

 

 

 

 

 

 

 

 

YES

 

NO

 

 

 

 

 

 

Excessive load?

the motor connected

Correct the wiring error.

 

 

 

 

 

 

 

 

YES

 

correctly?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the torque boost

YES

set correctly?

 

NO

The load is excessive, resulting in motor lock.

Reduce the load and check that the brake is released

(if a mechanical brake is used).

Note: Monitor the operation command or frequency setting values, etc., on the LED or LCD monitor after selecting

the respective functions.

Raise the torque boost.

The motor does not rotate if the following commands are issued.

An operation command is issued while the coast-to-stop or DC braking command is output

A reverse operation command is issued with the “H08 Rev. phase sequence lock” value set to 1.

7-5