FMP

Frequency monitor

 

Outputs a monitor signal using the pulse waveform.

 

 

Pulse output

(CM:

(pulse waveform output)

 

This signal has the same function as the FMA signal.

 

 

Common

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

terminal)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A running signal, frequency equivalence signal, overload early warning

 

Y1

Transistor output1

 

signal, and other signals from the

inverter are

output (as

transistor

 

 

 

 

output) to arbitrary ports, For details, see "Setting the

Terminal

 

Y2

Transistor output2

 

Functions E20 to E23" in Section 5.2, "Details of Each Function."

 

Y3

Transistor output3

 

 

<Specifications of transistor output circuit>

 

 

 

Y4

Transistor output4

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

min.

 

typ.

max.

 

 

 

 

 

Operating

 

ON level

 

-

 

2V

3V

 

 

 

 

 

voltage

 

OFF level

 

-

 

24V

27V

 

Transistor

 

 

 

Maximum load current at ON level

 

-

 

-

50mA

 

 

 

 

Leakage current at OFF level

 

-

 

-

0.1mA

 

output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CME

Transistor output

Common terminal for transistor output signals

 

 

common

This terminal is insulated from terminals [CM] and [11].

 

30A,30B,

Alarm output for any fault

If the inverter is stopped by an alarm (protective function), the alarm

 

30C

 

signal is output from the relay contact output terminal (1SPDT).

 

 

 

Contact rating: 48V DC, 0.5A

 

 

 

An excitation mode (excitation at alarm occurrence or at normal

Relay output

 

 

operation) can be selected.

Y5A,Y5C

Multipurpose-signal relay

These signals can be output similar to the Y1 to Y4 signals above.

 

 

 

output

The contact rating for any fault is the same as that of the alarm output

 

 

 

above.

 

 

 

An excitation mode (excitation at alarm occurrence or at normal

 

 

 

operation) can be selected.

 

DX+, DX-

RS-485 communication

Input-output signal terminals for RS-485 communication. UP to 31

Communication

 

input-output

inverters can be connected using the daisy chain method.

SD

Communication-cable

Terminal for connecting the shield of a cable. The terminal is

 

 

shield connection terminal

electrically floating.

(1)Analog input terminals (13,12,V2,C1,and 11)

These terminals receive weak analog signals that may be affected by external noise. The cables must be as short as possible (66ft (20m) or less), must be shielded, and must be grounded in principle. If the cables are affected by external induction noise, the shielding effect may be 0k to 5 kΩ improved by connecting the shield to terminal [11].

If contacts must be connected to these circuits, twin (bifurcated type) contacts for handling weak signals must be used. A contact must not be connected to terminal [11].

If an external analog signal output device is connected to these terminals, it may malfunction as a result of inverter noise. To prevent malfunction, connect a ferrite core or capacitor to the external analog signal output device.

Fig. 2-3-12

Fig. 2-3-13 Example of noise prevention

2-14

Page 26
Image 26
Fuji Bikes 5000G11S/P11S instruction manual Example of noise prevention