U23, U24
Related functions:

F14

Restart mode after momentary power failure

‹This function selects operation if a momentary power failure occurs.

The function for detecting power failure and activating protective operation (i.e., alarm output, alarm display, inverter output cutoff) for undervoltage can be selected. The automatic restart function (for automatically restarting a coasting motor without stopping) when the supply voltage is recovered can also be selected.

‹When setting value is selected "2" or "3", both integration constant and the proportional constant during operation ride-though can be adjusted by the function code : U23 and U24. The details are referred to the function code : U23 and U24.

F 1 4 R

E S T A R T

Setting range: 0 to 5

The following table lists the function details.

Set

Function name

Operation at power failure

Operation at power recovery

value

 

 

 

 

 

 

Inactive

 

 

If undervoltage is detected, the drive will immediately trip and

The drive operation is not automatically

 

(immediate inverter trip)

an undervoltage fault (LU) is displayed.

The drive output

restarted. Input a reset command and

 

 

 

 

stops and the motor will coast to a stop.

 

operation command to restart operation.

Inactive

 

 

If undervoltage is detected, the drive output stops and the

An undervoltage fault (LU) is activated at

 

(inverter trip at recovery)

motor will immediately coast to a stop. A drive fault is not

power recovery. Drive operation is not

 

 

 

 

activated

 

automatically restarted. Input a reset

 

 

 

 

 

 

command to restart operation.

Inactive

 

 

When the DC bus voltage reaches the continue operation

The drive operation is not automatically

 

(inverter

trip

after

voltage level (H15), a controlled deceleration to a stop occurs.

restarted. Input a reset command and

 

deceleration to a stop at

The inverter collects the inertia energy of the load to maintain

operation command to restart operation.

 

power failure) Note1

the DC bus voltage and controls the motor until it stops, then

 

 

 

 

 

an undervoltage fault (LU) is activated.

 

 

 

 

 

 

The drive will automatically decrease the deceleration time if

 

 

 

 

 

necessary. If the amount of inertia energy from the load is

 

 

 

 

 

small, and the undervoltage level is achieved before the motor

 

 

 

 

 

stops, the undervoltage fault is immediately activated and the

 

 

 

 

 

motor will coast to a stop.

 

 

Active

 

 

When the DC bus voltage reaches the continue operation

Operation is automatically restarted.

 

(operation

ride

through,

voltage level (H15), energy is collected from the inertia of the

For power recovery during ride-through the

 

for high-inertia loads) Note1

load to maintain the DC bus voltage and extend the ride

drive will accelerate directly to the original

 

 

 

 

through time. The drive will automatically adjust the

frequency. If undervoltage is detected,

 

 

 

 

deceleration rate to maintain DC bus

voltage level. If

operation automatically restarts with the

 

 

 

 

undervoltage is detected, the protective function is not

frequency at the time that the undervoltage

 

 

 

 

activated, but drive output stops and the motor coast to a stop.

is detected.

Active

 

 

If undervoltage is detected, the protective function is not

Operation is automatically restarted with

 

(restart

with

the

activated. The drive output stops and the motor will coast to a

the frequency at power failure.

 

frequency

at

power

stop.

 

 

 

failure) Note1

 

 

 

 

 

Active

 

 

If undervoltage is detected, the protective function is not

Operation is automatically restarted with

 

(restart with the start

activated, but output stops.

 

the frequency set by F23, "Starting

 

frequency, for low-inertia

 

 

frequency."

 

loads) Note1

 

 

 

 

 

 

 

 

 

 

 

 

Note1) When the function code H18(Torque control) is excluding "0" and Motor 1 is selected, the inverter will trip at power recovery if function code F14 is set to between "2" and "5". This operation is same as F14 is set to "1".

Function codes H13 to H16 are provided to control a restarting operation after momentary power failure. These functions should be understood and used. The pick-up (speed search) function can also be selected as a method of restarting when power is recovered following a momentary failure. (For setting details, see function code H09.)

The pick-up function searches for the speed of the coasting motor to restart the motor without subjecting it to excessive shock. In a high-inertia system, the reduction in motor speed is minimal even when the motor is coasting. A speed searching time is required when the pick-up function is active. In such a case, the original frequency may be recovered sooner when the function is inactive and the operation restarted with the frequency prior to the momentary power failure.

The pick-up function works in the range of 5 to 100 Hz. If the detected speed is outside this range, restart the motor using the regular restart function.

WARNING

Automatically restart could be provided at power recovered, if "Restart mode after momentary power failure" is valid.

The machine should be designed to securing the human safe even restarting.

Accident may result.

5-12

Page 59