Func

NAME

 

 

LCD Display

Setting range

Unit

Min.

Factory setting

Change

User

Remark

No.

 

 

Unit

 

 

 

during op

Set value

 

 

 

 

 

 

 

-30HP

 

40HP-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C20

JOG frequency

 

C20

JOG Hz

G11S:0.00 to 400.00Hz

Hz

0.01

5.00

A

 

 

 

 

 

 

 

P11S:0.00 to 120.00Hz

 

 

 

 

 

 

 

 

C21

PATTERN(Mode select)

 

 

PATTERN

0,1,2

-

-

0

 

NA

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

 

C22

 

(Stage 1)

C22

STAGE 1

Operation time:0.00 to 6000s

s

0.01

0.00

F1

A

 

 

C23

 

(Stage 2)

C23

STAGE 2

F1 to F4 and R1 to R4

 

 

0.00

F1

A

 

 

C24

 

(Stage 3)

C24

STAGE 3

 

 

 

0.00

F1

A

 

 

C25

 

(Stage 4)

C25

STAGE 4

 

 

 

0.00

F1

A

 

 

C26

 

(Stage 5)

C26

STAGE 5

 

 

 

0.00

F1

A

 

 

C27

 

(Stage 6)

C27

STAGE 6

 

 

 

0.00

F1

A

 

 

C28

 

(Stage 7)

C28

STAGE 7

 

 

 

0.00

F1

A

 

 

C30

Frequency command 2

 

C30

FREQ CMD 2

0 to 11

-

-

2

 

NA

 

 

C31

Offset adjust(terminal[12])

 

C31

BIAS 12

-100.0 to +100.0%

%

0.1

0.0

A

 

 

C32

 

 

C32

GAIN 12

0.0 to +200.0%

%

0.1

100.0

A

 

 

C33

Analog setting signal filter

 

C33

REF FILTER

0.00 to 5.00s

s

0.01

0.05

A

 

 

P:Motor Parameters

 

 

 

 

 

 

 

P01

Number of motor 1 poles

P01

M1 POLES

2 to 14

-

2

4

NA

P02

Motor 1

(Capacity) P02

M1-CAP

Up to 30[HP]: 0.01 to 60HP

HP

0.01

Motor Capacity

NA

 

 

 

 

40[HP]and above: 0.01 to 800HP

 

 

 

 

P03

 

(Rated current) P03

M1-Ir

0.00 to 2000A

A

0.01

Motor rated current

NA

P04

 

(Tuning) P04

M1 TUN1

0, 1, 2

-

-

0

NA

P05

 

(On-line Tuning) P05

M1 TUN2

0, 1

-

-

0

NA

P06

 

(No-load current) P06

M1-Io

0.00 to 2000A

A

0.01

Fuji STANDARD RATED

NA

 

 

 

 

 

 

 

VALUE

 

P07

 

(%R1 setting) P07

M1-%R1

0.00 to 50.00%

%

0.01

Fuji STANDARD RATED

A

 

 

 

 

 

 

 

VALUE

 

P08

 

(%X setting) P08

M1-%X

0.00 to 50.00%

%

0.01

Fuji STANDARD RATED

A

 

 

 

 

 

 

 

VALUE

 

P09

Slip compensation control 1

P09

SLIP COMP1

0.00 to 15.00Hz

Hz

0.01

0.00

A

H:High Performance Functions

 

 

 

 

 

 

H03

Data initializing

H03

DATA INIT

0, 1

-

-

0

NA

H04

Auto-reset

(Times) H04

AUTO-RESET

0, 1 to 10 times

-

1

0

A

H05

 

(Reset interval) H05

RESET INT

2 to 20s

s

1

5

A

H06

Fan stop operation

H06

FAN STOP

0, 1

-

-

0

A

H07

ACC/DEC pattern

(Mode select) H07

ACC PTN

0,1,2,3

-

-

0

NA

H08

Rev. phase sequence lock

H08

REV LOCK

0, 1

-

-

0

NA

H09

Start mode

H09

START MODE

0, 1, 2

-

-

0

NA

H10

Energy-saving operation

H10

ENERGY SAV

0, 1

-

-

G11S:0

A

 

 

 

 

 

 

 

P11S:1

 

H11

DEC mode

H11

DEC MODE

0, 1

-

-

0

A

H12

Instantaneous OC limiting

H12

INST CL

0, 1

-

-

1

NA

H13

Auto-restart

(Restart time) H13

RESTART t

0.1 to 10.0s

s

0.1

0.1

NA

H14

 

(Freq. fall rate) H14

FALL RATE

0.00 to 100.00Hz/s

Hz/s

0.01

10.00

A

H15

 

(Holding DC voltage) H15

HOLD V

3ph 230V class: 200 to 300V

V

1

230V class:235V

A

 

 

 

 

3ph 460V class: 400 to 600V

 

 

460V class:470V

 

H16

(OPR command selfhold time) H16

SELFHOLD t

0.0 to 30.0s, 999

s

0.1

999

NA

H18

Torque control

H18

TRQ CTRL

G11:0, 1, 2, P11:0

-

-

0

NA

H19

Active drive

H19

AUT RED

0, 1

-

-

0

A

H20

PID control

(Mode select) H20

PID MODE

0, 1, 2

-

-

0

NA

H21

 

(Feedback signal) H21

FB SIGNAL

0, 1, 2, 3

-

-

1

NA

H22

 

(P-gain) H22

P-GAIN

0.01 to 10.00 times

-

0.01

0.1

A

H23

 

(I-gain) H23

I-GAIN

0.0 , 0.1 to 3600s

s

0.1

0.0

A

H24

 

(D-gain) H24

D-GAIN

0.00s , 0.01 to 10.0s

s

0.01

0.00

A

H25

 

(Feedback filter)

FB FILTER

0.0 to 60.0s

s

0.1

0.5

A

H26

PTC thermistor

(Mode select) H26

PTC MODE

0, 1

 

 

0

A

H27

 

(Level) H27

PTC LEVEL

0.00 to 5.00V

V

0.01

1.60

A

H28

Droop operation

H28

DROOP

G11:-9.9 to 0.0Hz, P11:0.0 (Fixed.)

Hz

0.1

0.0

A

H30

Serial link

(Function select) H30

LINK FUNC

0, 1, 2, 3

-

-

0

A

H31

Modbus-RTU

(Address)

ADDRESS

0 (broadcast), 1 to 247

-

1

1

NA

H32

(Mode select on no response error)

MODE ON ER

0, 1, 2, 3

-

-

0

A

H33

 

(Timer)

TIMER

0.0 to 60.0s

s

0.1

2.0

A

H34

 

(Baud rate)

BAUD RATE

0, 1, 2, 3

-

-

1

A

H35

 

(Data length)

LENGTH

0 (8-bit fixed)

-

-

0

A

H36

 

(Parity check)

PARITY

0, 1, 2

-

-

0

A

H37

 

(Stop bits)

STOP BITS

0(2bit), 1(1bit)

-

-

0

A

H38

(No response error detection time)

NO RES t

0 (No detection), 1 to 60s

s

1

0

A

H39

 

(Response interval)

INTERVAL

0.00 to 1.00s

s

0.01

0.01

A

5-3

Page 50
Image 50
Fuji Bikes 5000G11S/P11S instruction manual PMotor Parameters, HHigh Performance Functions