F03

Maximum frequency 1

‹This function sets the maximum output frequency for motor 1.

‹This is a function for motor 1.

F

0

3

M A X

H

z

-

1

Setting range G11S: 50 to 400 Hz P11S: 50 to 120Hz

Setting a value higher than the rated value of the device to be driven may damage the motor or machine. Match the rating of the device.

F04

Base frequency 1

‹This function sets the maximum output frequency in the constant-torque range of motor 1 or the output frequency at the rated output voltage. Match the rating of the motor.

‹This is a function for motor 1.

F

0

4

B

A

S

E

 

H

z

-

1

 

 

 

Setting range G11S: 25 to 400Hz P11S: 25 to 120Hz

Note: When the set value of base frequency 1 is higher than that of maximum output frequency 1, the output voltage does not increase to the rated voltage because the maximum frequency limits the output frequency.

Output

Constant-torque range

voltage

 

 

 

F06 Maximum output voltage 1

F05 Rated voltage 1

Output frequency

0

F04 Base

F03 Maximum

 

frequency 1

output frequency

F05

Rated voltage 1

‹This function sets the rated value of the voltage output to motor 1. Note that a voltage greater than the supply (input) voltage cannot be output.

‹This is a function for motor 1.

F

0

5

R

A

T

E

D

 

 

V

-

1

 

 

Setting range 230 V series:

0,

80 to 240V

 

 

 

 

460 V series:

0,

320 to 480V

Value 0 terminates operation of the voltage regulation function, thereby resulting in the output of a voltage proportional to the supply voltage.

Note: When the set value of rated voltage 1 exceeds maximum output voltage 1, the output voltage does not increase to the rated voltage because the maximum output voltage limits the output voltage.

F06

Maximum voltage 1

‹This function sets the maximum value of the voltage output for motor 1. Note that a voltage higher than the supply (input) voltage cannot be output.

‹This is a function for motor 1.

F

0

6

M

A

X

 

V

-

1

 

 

 

 

 

 

 

Setting range

 

230 V series:

80 to 240V

 

 

 

 

 

460 V series:

320 to 480V

Note: When the set value of rated voltage 1 (F05) to "0", this function is invalid.

F07

Acceleration time 1

F08

Deceleration time 1

‹This function sets the acceleration time for the output frequency from startup to maximum frequency and the deceleration time from maximum frequency to operation stop.

F

0

7

A

C

C

 

T

I

M

E

1

 

F

0

8

D

E

C

 

T

I

M

E

1

 

Setting range Acceleration time 1: 0.01 to 3,600 seconds Deceleration time 1: 0.01 to 3,600 seconds

Acceleration and deceleration times are represented by the three most significant digits, thereby the setting of three high-order digits can be set.

Set acceleration and deceleration times with respect to maximum frequency. The relationship between the set frequency value and acceleration/deceleration times is as follows:

Set frequency = maximum frequency

The actual operation time matches the set value.

FWD

STOP

frequencyOutput

Maximum frequency

 

 

Set frequency

 

Time

Acceleration time

Deceleration time

Set frequency < maximum frequency

The actual operation time differs from the set value. Acceleration(deceleration) operation time = set value x (set frequency/maximum frequency)

FWD

STOP

frequency

Maximum frequency

Set frequency

Output

 

Acceleration

Time

Deceleration

operation time

operation time

 

Acceleration time

Deceleration time

Note: If the set acceleration and deceleration times are too short even though the resistance torque and moment of inertia of the load are great, the torque limiting function or stall prevention function becomes activated, thereby prolonging the operation time beyond that stated above.

5-9

Page 56
Image 56
Fuji Bikes 5000G11S/P11S F03 Maximum frequency, F04 Base frequency, F05 Rated voltage, F06 Maximum voltage