High Performance functions (H:High Performance function)

H03

Data initializing

‹This function returns all function data changed by the customer to the factory setting data. (initialization).

W hen retry succeeded

Occurrence Extinction

 

H

0

3

D

A

T

A

 

I

N

I

T

 

 

 

 

 

 

 

 

 

 

Set value 0Disabled.

 

 

 

 

 

 

 

 

 

 

 

 

 

1Initializing data.

 

 

 

 

 

 

 

 

 

 

‹To perform initialization, press the

STOP

and

 

keys

together to set 1, then press the

FUNC

key.

The set

 

 

 

 

 

 

 

 

 

 

 

DATA

 

 

 

 

 

values of all functions are initialized. The set value in H03 automatically returns to 0 following the end of

initialization.

 

H04

Auto-reset(Times)

H05

Auto-reset (Reset interval)

‹When the inverter protective function which invokes the retry operation is activated, this function releases operation of the protective function and restarts operation without issuing an alarm or terminating output.

Alarm

Automatic release command of protective function

Output frequency

Output signals

terminals Y1 to Y5

 

 

 

 

 

 

 

0.1S

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W aiting time

 

 

 

 

 

 

 

 

(H05)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Restart

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5min. after

RESET the times

 

 

 

 

 

 

 

 

constant speed

of auto-reset

 

 

 

 

 

 

 

 

 

 

 

ON

H

0

4

A

U

T

O

-

R

E

S

E

T

H

0

5

R

E

S

E

T

 

I

N

T

 

Set the protective function release count and waiting time from its operation startup to release.

Setting range (Count)

: 0, 1 to 10

(Waiting time)

: 2 to 20 seconds

retry failed

 

 

Alarm

 

Occurrence

 

Extinction

reset

Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To not use the retry function, set 0 to "H04 Retry (count)." ‹Inverter protective functions that can invoke retry

function.

OC1,OC2,OC3

dBH

: Overcurrent

: Braking resistor overheating

OV1,OV2,OV3

OL1

: Overvoltage

: Motor 1 overload

OH1

OL2

: Heat sink overheating

: Motor 2 overload

OH3

OLU

: Inverter inside overheating

: Inverter overload

‹When the value of "H04 Retry (count)," is set from 1 to 10, an inverter run command is immediately entered

Automatic release command of protective function Output frequency

Output signals

terminals Y1 to Y5

0.1S

 

 

 

 

0.1S

 

 

 

 

 

 

 

0.1S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H05:

 

 

 

 

 

 

H05:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Retry

W ait

 

 

W ait

 

 

 

 

 

 

 

 

 

 

 

 

 

 

end

time

 

 

 

 

time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Count set in

 

 

 

 

 

First

 

 

 

 

Second

H04 (count)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

following the wait time set in H05, "Retry (wait time)," and the startup of the retry operation. If the cause of the alarm has been removed at this time, the inverter starts without switching to alarm mode. If the cause of the alarm still remains, the protective function is reactivated according to the wait time set in "H05 Retry (waiting time)." This operation is repeated until the cause of the alarm is removed. The restart operation switches to alarm mode when the retry count exceeds the value set in "H04 Retry (count)."

The operation of the retry function can be monitored from terminals Y1 to Y5.

 

When the retry function is selected,

 

operation automatically restarts depending

WARNING

on the cause of the trip stop. (The

machine should be designed to ensure

 

safety during a restart)

as accident may result.

H06

Fan stop operation

‹This function specifies whether cooling fan ON/OFF control is automatic. While power is applied to the inverter, the automatic fan control detects the temperature of the cooling fan in the inverter and turns the fan on or off.

When this control is not selected, the cooling fan rotates continually.

H

0

6

F

A

N

 

S

T

O

P

 

 

Set value 0: ON/OFF control disabled. 1: ON/OFF control enabled.

The cooling fan operating status can be monitored from terminals Y1 to Y5.

5-34

Page 81
Image 81