3.Operation

3-1 Inspection and Preparation before Operation

Check the following before operation:

Check that the connection is correct.

In particular, check that the power supply is not connected to any of the U, V, and W output terminals and that the ground terminal is securely grounded.

Check for short-circuits and ground faults between the terminals and live sections.

Check for loose terminals, connectors, or screws.

Check that the motor is separated from mechanical equipment.

Turn off switches before turning power to ensure that the inverter will not start or operate abnormally at power-on.

Check the following after power-on:

a.Check that no alarm message is displayed on the keypad panel (see Figure 3-1-2).

b.Check that the fan inside the inverter is rotating. (For inverters with 2HP or more)

Fig. 3-1-1 Inverter connection

WARNING

Be sure to put on the surface cover before turning on the power (close). Never remove the cover while the power is applied to the inverter.

To ensure safety, do not operate switches with wet hands.

Electric shock may result

Fig. 3-1-2

Display on keypad panel at power-on

3-2 Operation Method

There are various methods of operation. Select a method of operation according to operating purpose and specifications by referring to Section 4-2, "Operating the Keypad Panel," and Chapter 5, "Explanation of Functions." Table 3-2-1 lists general operation methods

3-3 Trial Run

Upon confirming that inspection results are normal (see Section 3-1), proceed with a trial run. The initial operation mode (set at factory) is using the keypad panel.

Turn power on and confirm that frequency

Table 3-2-1 General operation methods

 

display 0.00Hz is blinking on the LED monitor.

Operation

 

 

Frequency setting

Operation

Set the frequency to about 5Hz using

 

 

key.

command

 

 

command

 

 

 

 

 

 

 

Operation

Keys on keypad panel

 

 

 

 

To start the run, press

 

key (for

forward

FWD

 

REV

 

FWD

using keypad

 

 

 

 

 

 

 

 

 

 

 

rotation) or

REV

key (for

reverse rotation). To

panel

 

 

 

 

STOP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

stop, press

STOP

key.

 

 

 

 

 

Operation

 

 

 

 

 

 

Contact input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check the following items :

 

 

 

 

using

 

 

 

 

(switch)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a. Is the rotating direction correct?

 

 

external

 

 

 

 

 

 

Terminals

 

 

 

Freq. Setting POT (VR),

 

b. Is the rotation smooth? (no buzzing or

signal

analog voltage,

FWD-CM and

 

abnormal vibration)

 

 

 

 

 

terminals

analog current

REV-CM

c. Is acceleration and deceleration smooth?

If no abnormality is detected, increase the frequency and check the above items again. If the results of the trial run are normal, start a formal run.

Notes: - If an error is detected in the inverter or motor, immediately stop the operation and attempt to determine the cause of error referring to Chapter 7, "Troubleshooting."

-As voltage is still applied to the main circuit terminals (L1/R, L2/S, L3/T) and auxiliary control-power terminals (R0, T0) even when the output from the inverter is terminated, do not touch the terminals. The smoothing capacitor in the inverter is being charged after the power is turned off and it is not discharged immediately. Before touching an electric circuit, confirm that the charge lamp is off or a multimeter is indicating a low voltage at the terminals.