6-2 Alarm Reset

To release the trip status, enter the reset command by pressing the RESET key on the keypad panel or inputting signal from the terminal (RST) of the control terminals after removing the cause of the trip. Since the reset command is an edge operation, input a command such as !!OFF-ON-OFF!! as shown in Fig.6-2-1.

10ms

Reset command

OFF

ON

Keypad panel display

Alarm display

or

OFF

Normal display

(Operable)

When releasing the trip status, set the operation command to OFF. If the operation command is set to ON, inverter will start operation after resetting.

Alarm output

OFF

ON

OFF

Trip Fig.6-2-1

WARNING

If the alarm reset is activated with the operation signal ON, the inverter will restart suddenly, which may be dangerous. To ensure safety, disable the operating signal when releasing the trip status.