Related functions:
E01 to E09
(Set value 17,18)
Related functions:
C21to C28
Related functions:
E01 to E09
(Set value 21)

5-2 Function Explanation

F:Fundamental function

F00

Data protection

‹Setting can be made so that a set value cannot be

changed by keypad panel operation.

 

Related functions

0

D

A

T

A

P

R

T

C

E01 to E09

 

 

 

 

 

 

 

 

 

(Set values 19)

Setting range

 

0

: The data can be changed.

[Setting procedure ]

1

: The data cannot be changed.

 

 

 

 

 

 

 

0 to 1: Press the

STOP

and

keys simultaneously

to change the value from 0 to 1, then press the

FUNCDATA

to validate the change.

1 to 0: Press the STOP and

keys simultaneously

to change the value from 1 to 0, then press the

FUNC

key to validate the change.

DATA

F01

Frequency command 1

Forward / Inverse operation

 

 

 

Frequency setting value

 

 

 

Forward operation

 

 

 

 

 

 

 

 

(set value: 1, 3, 4, 5)

Maximum frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverse operation

 

 

 

 

 

 

 

 

 

 

 

Set value:1,3

 

 

 

(set value::6)

 

 

 

 

 

 

 

 

 

 

-10

0

 

+10 [V]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog input terminal

 

 

 

 

[12] , [V2]

 

 

 

 

 

 

 

 

 

 

Related functions:

 

 

 

 

 

 

 

 

 

 

 

 

value:4,5

 

 

 

E01 to E09

 

- Maximum frequency

 

 

 

(Set value 21)

 

‹This function selects the frequency

Related functions

 

 

 

 

 

 

 

setting method.

 

 

 

 

 

 

E01 to E09

 

Frequency setting value

Forward operation

 

 

 

 

 

 

 

 

 

 

 

 

(Set values 17,18)

 

(set value: 2)

 

 

F

R

E

Q

 

C

M

D

1

 

C30

 

Maximum frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

: Setting by keypad panel operation (

 

 

 

key)

1

: Setting by voltage input (terminal [12

](0 to

 

+10V)

 

+terminal [V2](0 to +10V) )

2:Setting by current input (terminal [C1] (4 to 20mA)).

3:Setting by voltage input + current input (terminal [12]

+terminal [C1] ) (-10 to +10V + 4 to 20mA).

4:Reversible operation with polarity ( terminal [12]

(-10 to +10V))

5:Reversible operation with polarity ( terminal [12] +[V2]+[V1](Option) (-10 to +10V))

6:Inverse mode operation

(terminal [12] +[V2] (+10V to 0 ))

7: Inverse mode operation (terminal [C1] (20 to 4mA))

8: Setting by UP/DOWN control mode 1 (initial value = 0) (terminals [UP] and [DOWN])

9: Setting by UP/DOWN control mode 2 (initial value =last final value) (terminals [UP] and [DOWN])

See the function explanation of E01 to E09 for details. 10: Setting by pattern operation

See the function explanation C21 to C28 for details. 11: Setting by digital input or pulse train

* Optional. For details, see the instruction manual on options.

Inverse operation (set value: 7)

0

 

 

 

 

0

4

20 [mA]

 

 

 

Analog input terminal

 

 

 

[C1]

F02

Operation method

‹This function sets the operation command input method.

F

0

2

O

P

R

 

M

E

T

H

O

D

Setting range 0: Key pad operation

(

FWD

REV

STOP

keys).

Press the

FWD

for forward operation.

Press the

REV

for reverse operation.

Press the

STOP

for deceleration to a stop.

Input from terminals [FWD] and [REV] is

ignored.

 

 

 

(LOCAL)

 

 

STOP key active)

1: Terminal operation(

2:Terminal operation( STOP

3:Terminal operation( STOP with Fuji start software.

4:Terminal operation( STOP with Fuji start software.

key inactive)

key active)

key inactive)

*- This function can only be changed when terminals FWD and REV are open.

- REMOTE/LOCAL switching from the keypad panel automatically changes the set value of this function.

- REMOTE/LOCAL can be changed by pressing the STOP key and RESET key simultaneously.

5-7

Page 54
Image 54
Fuji Bikes 5000G11S/P11S instruction manual Function Explanation