Instructions on maintenance, inspection, and replacement
WARNING
•Wait a minimum of five minutes (30HP or less) or ten minutes (40HP or more) after power has been tumed off (open) before starting inspection. (Also confirm that the charge lamp is off and that DC voltage between terminals P (+) and N
Electrical shock may result.
•Only authorized personnel should perform maintenance, inspection, and replacement operations.(Take off metal jewelry such as watches and rings. Use insulated tools.)
Electric shock or injury may result.
Instructions on disposal
CAUTION
•Treat as industrial waste when disposing it.
Injury may result.
Other instructions
WARNING
•Never modify the product.
Electric shock or injury may result.
Conformity to Low Voltage Directive in Europe
CAUTION
•The contact capacity of alarm output for any fault (30A, B, C) and relay signal output (Y5A, Y5C) is 0.5A at 48V DC.
•The ground terminal G should be connected to the ground.
Use a crimp terminal to connect a cable to the main circuit terminal or inverter ground terminal.
•Where RCD
Otherwise another protective measure shall be applied such as separation of the EE from the environment by double or reinforced insulation or isolation of EE and supply system by the transformer.
•Use a single cable to connect the G inverter ground terminal. (Do not use two or more inverter ground terminals.)
•Use a
•Use the inverter under
•For the
•To ensure safety, install an optional AC reactor, DC reactor, or external braking resistor as follows:
1)Install inside an IP4X cabinet or barrier if electrical parts are exposed.
2)Install inside an IP2X cabinet or barrier if electrical parts are not exposed.
•It is necessary to install the inverter in appropriate method using an appropriate RFI filter to conform to the EMC directive. It is customer's responsibility to check whether the equipment, the inverter is installed in, conforms to EMC directive.