8. Maintenance and Inspection

Proceed with daily inspection and periodic inspection to prevent malfunction and ensure long-term reliability. Note the following:

8-1 Daily Inspection

During operation, a visual inspection for abnormal operation is completed externally without removing the covers

The inspections usually cover the following:

(1)The performance (satisfying the standard specification) is as expected.

(2)The environment satisfies standard specifications.

(3)The keypad panel display is normal.

(4)There are no abnormal sounds, vibrations, or odors.

(5)There are no indications of overheating or no discoloration.

8-2 Periodical Inspection

Periodic inspections must be completed after stopping operations, cutting off the power source, and removing the surface cover.

Note that after turning off the power, the smoothing capacitors in the DC section in the main circuit take time to discharge. To prevent electric shock, confirm using a multimeter that the voltage has dropped below the safety value (25 V DC or below) after the charge lamp (CRG) goes off.

 

 

 

Start the inspection at least five minutes after turning off the power supply for

 

 

 

 

inverter rated at 30HP or less, and ten minutes for inverter rated at 40HP or

 

 

 

 

more. (Check that the charge lamp (CRG) goes off, and that the voltage is 25V

 

 

 

 

DC or less between terminals P(+) and N(-). Electric shock may result.

 

WARNING

Only authorized personnel should perform maintenance and component

 

 

replacement operations. (Remove metal jewelry such as watches and rings.)

 

 

 

 

 

 

 

(Use insulated tools.))

 

 

 

Never modify the inverter.

 

 

 

 

Electric shock or injury may result.

 

 

 

 

 

Table 8-2-1 Periodical inspection list

 

Check parts

 

Check items

 

How to inspect

Evaluation Criteria

Environment

1)

Check the ambient temperature, humidity,

1) Conduct visual

1) The specified

 

 

 

vibration, atmosphere

(dust, gas, oil

mist,

inspection and use

standard value

 

 

 

water drops).

 

 

must be satisfied.

 

 

 

 

 

the meter.

 

 

2)

Is the area surrounding the equipment clear

2) The area is clear.

 

 

2) Visual inspection

 

 

 

of foreign objects.

 

 

 

 

 

 

 

 

 

 

Keypad panel

1) Is the display hard to read?

 

1),2) Visual inspection

1),2) The display can

 

 

2)

Are the characters complete?

 

 

be read and is not

 

 

 

 

 

 

 

abnormal.

Structure such as a

1)

Is there abnormal sound or vibration?

 

1) Visual and aural

1), 2), 3), 4), 5) Not

frame or cover

2)

Are nuts or bolts loose?

 

inspection

abnormal

 

 

3)

Is there deformation or damage?

 

2) Tighten.

 

 

 

4)

Is there discoloration as a result of

 

3),4),5) Visual

 

 

 

 

overheating?

 

 

inspection

 

 

 

5)

Are there stains or dust?

 

 

 

 

Common

1)

Are there loose or missing nuts or bolts?

 

1) Tighten.

1), 2), 3) Not

 

 

2)

Are there deformation, cracks, damage, and

2),3) Visual inspection

abnormal

circuit

 

3)

discoloration due

to overheating

or

 

Note: Discoloration

 

Are there stains and dust?

 

 

not indicate a

 

 

 

deterioration in the equipment and insulation?

 

of the bus bar does

Main

 

 

 

 

 

 

problem.

Conductor and

1)

Is there discoloration or distortion of a

 

1),2) Visual inspection

1), 2) Not abnormal

 

wire

 

conductor due to overheating?

 

 

 

 

 

2)

Are there cracks, crazing or discoloration of

 

 

 

 

 

the cable sheath?

 

 

 

 

8-1

Page 104
Image 104
Fuji Bikes 5000G11S/P11S instruction manual Maintenance and Inspection, Periodical inspection list, Environment