Inverter stopping [STOP]

This function outputs an inverted signal to Running (RUN) to indicate zero speed. An ON signal is output when the DC injection brake function is operating.

Ready output [RDY]

This function outputs an ON signal when the inverter is ready to operate. The inverter is ready to operate when the main circuit and control circuit power is established and the inverter protective function is not activating. About one second is required from power-on to ready for operation in normal condition.

Line/Inv changeover [SW88] [SW52-2] [SW52-1]

To perform switching operation between the line and the inverter, the sequence prepared in the inverter can be used to select and output signals for opening and closing the magnetic contactors connected to the inverter. As the operation is complex, refer to technical documentation for the FRENIC5000G11S series when using this function.

As the sequence will operate automatically when SW88 or SW52-2 is selected, do not select when not using the sequence.

Motor 2 /Motor 1 [SWM2]

When a signal for switching to motor 2 is input from the terminal selected by terminals [X1] to [X9], this function selects and outputs the signal for switching the magnetic contactor for the motor. As this switching signal is not output during running including when the DC injection braking function is operating, a signal must be re-input after output stops.

Auxiliary terminal [AX]

When an operation (forward or reverse) command is entered, this function outputs an ON signal. When a stop command is entered, the signal goes off after inverter output stops. When a coast-to-stop command is entered and the inverter protective function operates, the signal goes off immediately.

Time-up signal for pattern operation [TU]

When the pattern operation stage changes, this function outputs a one-shot (100ms) ON signal to report a stage change.

Cycle completion signal for pattern operation [TO]

When the seven stages of a pattern operation are completed, this function outputs a one-shot (100 ms) ON signal to report the completion of all stages.

Stage No. indication for pattern operation [STG1] [STG2] [STG4]

During pattern operation, this function reports the stage (operation process) being operated.

Pattern operation

 

Output terminal

stage No.

 

STG1

STG2

STG4

 

 

Stage 1

 

 

 

 

off

off

Stage 2

 

off

 

off

Stage 3

 

 

 

 

 

off

Stage 4

 

off

off

 

Stage 5

 

 

 

 

off

 

Stage 6

 

off

 

 

Stage 7

 

 

 

 

 

 

When pattern operation is not activated (i.e., no stage is selected), the terminals do not output a signal.

Alarm indication [AL1] [AL2] [AL4] [AL8]

This function reports the operating status of the inverter protective function.

Alarm detail

Output terminal

(inverter protective function)

 

 

 

 

 

AL1

AL2

AL4

AL8

 

Overcurrent, ground fault, fuse blown

 

off

off

off

Overvoltage

off

 

off

off

Undervoltage shortage, input phase failure

off

 

off

off

Motors 1 and 2 overload

off

 

 

off

Inverter overload

off

off

 

 

off

Heat sink overheating, inverter inside overheating

 

 

 

off

External alarm input, braking resistor overheating

off

 

 

 

off

Memory error, CPU error

off

off

 

Keypad panel communication error, option communication error

off

off

off

 

Option error

 

off

 

Output wiring error

off

off

 

 

 

RS-485 communication error

off

off

 

 

 

Overspeed, PG disconnection

 

 

 

 

In normal operation terminals do not output a signal.

Fan operation signal [FAN]

When used with "H06 Cooling fan ON/OFF control," this function outputs a signal while the cooling fan is operating.

Auto-resetting [TRY]

When a value of 1 or larger is set to "H04 Retry operating," the signal is output while retry operation is activating when the inverter protective function is activated.

Universal DO [U-DO]

Assigning value "27" to a transistor output terminal renders the terminal a universal DO terminal.

This function enables ON/OFF through the RS-485 and BUS option.

This function serves only to turn on and off the transistor output through communication and is not related to inverter operation.

Overheat early warning [OH]

This function outputs a early warning signal when heat sink temperature is (overheat detection level - 10) or higher.

Life expectancy detection signal [LIFE]

‹When either of data for the Life expectancy judgment of the function code:U09 to U11 reaches at the Life expectancy judgment level, the ON signal is output. However, the inverter does not do alarm.

Moreover, the alarm output for any fault (30A, 30B, 30C ) does not operate.

Function

Parts of

Life expectancy

code

Life expectancy judgment

judgment level

U09

Capacitor in main circuit

85% or less of the initial value

U10

Electrolytic capacitor on PCB

61,000 hours

U11

Cooling fan

25,000 hours

U59

DC fan broken for stir internal

DC fan is broken

 

unit up

 

 

[40HP or more is corresponded.]

 

5-24

Page 71
Image 71
Fuji Bikes 5000G11S/P11S instruction manual STG1 STG2 STG4, AL1, AL4 AL8