(2) If the motor rotates but the speed does not change

The motor rotates but the speed does not change.

Is the maximum

YES

 

 

frequency

Increase the setting.

 

setting too low?

 

 

 

 

NO

 

 

YES

Is the higher or lower

 

 

 

Set the frequency.

 

 

Change the setting.

frequency limiter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

activating?

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

Keypad panel

Does the speed change

 

 

 

 

 

 

operation

NO

 

 

 

 

 

 

when the

or

 

 

 

 

 

 

 

key is pressed?

 

 

 

Pattern

Which frequency setting

 

 

 

 

 

 

 

 

 

YES

methodis used: keypad

 

 

 

 

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

panel, analog signal,

 

 

 

 

 

 

 

 

 

Is the timer

 

 

 

 

 

 

 

 

 

 

 

multistep frequency,

 

 

 

Can the frequency

 

 

timing too long?

 

 

 

 

 

 

 

or UP/DOWN control?

 

 

 

setting signal(0 to

 

 

 

 

 

Analog signal

 

YES

 

NO

 

Is the pattern operation

 

 

±10V,

 

 

 

 

 

 

 

 

 

 

 

 

 

activated?

 

 

 

4 to 20 mA)

 

 

YES

Is the pattern

 

 

 

 

 

be changed?

 

 

 

 

Multistep frequency

 

 

 

 

 

 

 

operation complete?

 

 

NO

 

 

 

 

UP/DOWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are the external

 

 

 

Are the external

NO

Correct the

 

 

NO

connections

 

Are all acceleration

 

connections between

 

 

between control

YES

 

 

connection error.

 

 

and deceleration

 

X1-X9 and CM correct?

 

 

 

terminals 13, 12, 11,

 

 

 

 

 

 

 

 

times identical?

 

YES

 

 

 

 

 

,V2 and C1 correct?

 

 

 

 

 

 

 

 

 

 

YES

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are the frequencies

NO

Change the

 

 

Replace the faulty

 

 

 

for each multistep

 

 

frequency setting

 

 

 

 

frequency setting.

 

 

 

 

frequency different?

 

 

POT (VR) or signal

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

converter as required.

 

 

 

 

 

 

 

 

 

 

 

Faulty inverter or error

NO

 

Is the acceleration

due to noise, etc.

 

or deceleration time

 

 

 

Contact Fuji Electric.

 

 

 

set too long?

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

Change the time setting

 

 

 

to conform to load values.

 

 

 

 

 

 

 

In the following cases, changing the motor speed is also restricted:

Signals are input from control terminals both 12 and C1 when F01 Frequency command 1and C30 Frequency command 2are set to 3, and there is no significant change in the added value

The load is excessive, and the torque limiting and current limiting functions are activated

7-6