Section 5. SPECIFICATIONS

VISTA-40 CONTROL

Physical: 12-1/2"W X 14-1/2"H X 3"D

Electrical:

 

VOLTAGE INPUT:

Ademco No. 1361 Plug-In Transformer (use 1361CN in Canada) or 4300

 

transformer (for X-10 installations) rated 16.5VAC, 40 VA.

ALARM SOUNDER OUTPUT: 10VDC-13.8VDC, 2.8 amps max., 750mA less aux. current draw

 

(UL1023/UL985 installations).

AUXILIARY POWER OUTPUT:

9.6VDC-13.8VDC, 750mA max. For UL installations, the accessories

 

connected to the output must be UL Listed, and rated to operate in the above

 

voltage range.

BACK-UP BATTERY:

12VDC, 4AH or 7AH gel cell. YUASA NP4-12 (12V, 4AH) or NP7-12 (12V,

 

7AH) recommended.

STANDBY:

4 hours min. with 750 mA aux. load using 7 AH battery.

CIRCUIT PROTECTORS:

Thermal circuit breakers are used on battery input to protect against reverse

 

battery connections and on alarm sounder output to protect against wiring

 

faults (Shorts).

 

A solid state circuit breaker is used on auxiliary power output to protect against

 

wiring faults (shorts).

DIGITAL COMMUNICATOR

FORMATS SUPPORTED:

ADEMCO HIGH SPEED

ADEMCO 4+2 EXPRESS

ADEMCO LOW SPEED

ADEMCO CONTACT ID

SESCOA

RADIONICS LOW SPEED

LINE SEIZE: Double Pole

RINGER EQUIVALENCE: Ê0.7B

FCC REGISTRATION No.: ÊAC398U-68192-AL-E

6 1 2 8 REMOTE KEYPAD

6 1 3 7 REMOTE KEYPAD

6 1 3 9 REMOTE KEYPAD

6 1 3 9 A V REMOTE KEYPAD

1.Physical: 5-3/4" W x 4-3/4" H x 1" D (146mm x 121mm x 26mm)

2.Electrical: Voltage Input: 12VDC; Current Drain: 30mA

3.Interface Wiring:

RED: 12VDC input (+) auxiliary power

BLUE: Not Used, if present

GREEN: Data to control panel

YELLOW: Data from control panel

BLACK: Ground and (-) connection from supplemental power supply.

1.Physical: 6-1/4" W x 4-3/4" H x 1" D (159mm x 121mm x 26mm)

2.Electrical: Voltage Input: 12VDC; Current Drain: 85mA

3.Interface Wiring: Same as 6128.

1.Physical: 6-1/4" W x 4-3/4" H x 1" D (159mm x 121mm x 26mm)

2.Electrical: Voltage Input: 12VDC; Current Drain: 100mA

3.Interface Wiring: Same as 6128.

1.Physical: 6-1/4" W x 4-3/4" H x 1" D (159mm x 121mm x 26mm)

2.Electrical: Voltage Input: 12VDC; Current Drain: 200mA

3.Interface Wiring: See 2-WAY VOICE KEYPADS & AUDIO ALARM ÊVERIFICATION (AAV) section.

Ð 110 Ð

Page 110
Image 110
Guardian Technologies N7001V2, VISTA-40 installation instructions Specifications, Digital Communicator