Section 5. ZONE CONFIGURATIONS

BASIC 9 HARD-WIRED ZONES

General Information

Zones 1-9 are reserved for traditional hard-wired devices. The following table summarizes zone usage.

Zone 1

EOLR supervised or closed circuit unsupervised devices. Also

 

supports up to sixteen (16) 2-wire smoke detectors.

Zones 2, 3, 4, 6

EOLR supervised or closed circuit unsupervised devices. Also

 

supports 4-wire smoke detectors.

Zone 5

EOLR supervised or closed circuit unsupervised devices. Also

 

supports 4-wire smoke detectors.

Zone 7

EOLR supervised or closed circuit unsupervised devices. Also

 

supports 4-wire smoke detectors. Alternatively, can be used to

 

support remote keyswitch. If used for keyswitch, it cannot be used

 

as protection zone.

Zone 8

EOLR supervised or closed circuit unsupervised devices. Also

 

supports 4-wire smoke detectors. Zone 8 also supports latching

 

glass break detectors.

Zone 9

Unsupervised devices only. Programmable for fast response

 

(10mS). Can monitor fast acting glass break detectors or vibration

 

sensors if set for fast response.

 

 

Programmable Response Time For Zone 9:

Zone response time for zone 9 can be set to either 350mS (normal) or 10mS (fast) via program field *14.

Hard-wired Zone 1

UL NOTE: EOLRs are required for UL installations.

Applications

Can be used for EOLR supervised or closed circuit

 

unsupervised devices. It is the only zone that supports up to

 

sixteen (16) 2-wire smoke detectors.

 

 

Zone Response Type

Any, except type 23 (no alarm)

 

 

Max. Zone Resistance

100 ohms, excluding EOLR

 

 

 

Unsupervised Usage

¥

Cut red PCB jumper.

 

¥

Only closed circuit devices can be used.

 

 

 

EOLR Supervised

¥

Leave red PCB jumper intact.

 

¥

Supports both open circuit and closed circuit devices.

 

¥

Connect open circuit device in parallel across the loop. The

 

 

2,000 ohm EOLR must be connected across the loop wires

 

 

at the last device.

 

¥

Connect closed circuit device in series with the loop.

 

 

 

EOLR Fire Zone:

¥

Leave red PCB jumper intact.

 

¥

Assign zone type 09 (fire)

 

¥

Supports up to sixteen (16) 2-wire smoke detectors.

 

¥

Second CODE + OFF sequence momentarily interrupts

 

 

power to reset the smoke detectors.

 

¥

See table that follows for compatible detectors.

 

 

 