Fault Annunciation

Since the phone module, RF receiver(s), VIM and the polling loop are shared

 

among the 2 partitions, the scheme for annunciating their failure follows:

 

Respective faults (for zones 87, 88Ð91, 93 & 97) will report as trouble conditions

 

only, and as such, should be assigned either zone type 00 if no annunciation is

 

desired, or zone type 05 if annunciation as trouble condition is desired. If the

 

polling loop or RF link fails, the corresponding zone number will display a trouble

 

condition for each partition that uses the device that failed. In addition, all zones

 

associated with that device will indicate a check condition. The trouble condition

 

will not interfere with the ability to arm the partition, but the faults must first be

 

bypassed.

 

 

 

 

NOTE: 5800 series transmitters have built-in tamper protection and will

 

annunciate a "CHECK" condition if cover is removed unless field *24 is disabled.

Important Battery Notice

The wireless transmitters are designed to provide long battery life under normal

 

operating conditions. Longevity of batteries may be as much as 4Ð7 years

 

depending on the environment, usage, and the specific wireless device being

 

used. External factors such as humidity, high or low temperatures, as well as large

 

swings in temperature may all reduce the actual battery life in a given installation.

 

The wireless system can identify a true low battery situation, thus allowing the

 

dealer or user of the system time to arrange a change of battery and maintain

 

protection for that given point within the system.

 

Button type transmitters should be periodically tested by the user for battery life

 

(ex. 5701, 5801, 5802, 5802MN, 5802CP, 5804).

Compatible 5700 Series

5701

Panic Transmitter

Wireless Devices

 

Programmable for either silent or audible 24-hour alarm (can be DIP

 

 

switch programmed for zones 62 or 63).

 

 

5711

Slimline Door/Window Transmitter

 

 

Can be used with any closed circuit sensor. Can be used on any

 

 

zone 1Ð63 but, if set for zones 32-47, there will be a 3-minute lock-

 

 

out between transmissions.

 

 

5 7 1 1 W M

Door/Window Transmitter w/Reed Switch

 

 

Can be used with any closed circuit sensor, on any zone 1Ð63 but, if

 

 

set for zones 32Ð47, there will be a 3-minute lock-out between

 

 

transmissions.

 

 

5 7 1 5 W H

Universal Transmitter

 

 

DIP switch selectable for fast response, open or closed circuit sensor

 

 

usage, and has a tamper protected cover. Use in applications where

 

 

open circuit heat detectors are needed or where fast response

 

 

devices are needed. Can be used on any zone 1-63 but, if set for

 

 

zones 32Ð47, there will be a 3-minute lock-out between

 

 

transmissions.

 

 

5727

Wireless Keypad

 

 

The keypad is identified as zone "00" when it transmits low battery

 

 

messages. The keypad panics are identified in the same way as wired

 

 

keypad panics (i.e. 95, 96 & 99).

 

 

5716

Door/Window Transmitter

 

 

Can be used with any open or closed circuit sensor (DIP switch

 

 

selectable), and features a built-in reed switch. Can be used on any

 

 

zone 1-63 but, if set for zones 32-47, there will be a 3 minute lock-out

 

 

between transmissions.

 

 

5775

Wireless PIR

 

 

DIP switch programmable for zones 32Ð47.

 

 

NOTE: There is a 3-minute lock-out between transmissions to

 

 

preserve battery life.

 

 

5706

Wireless Photoelectric Smoke Detector (System Sensor)

 

 

DIP switch programmable for zones 48Ð55.

 

 

5707

Wireless Photoelectric Smoke Detector (ESL)

 

 

DIP switch programmable for zones 48Ð55.

 

Ð 26 Ð

Page 26
Image 26
Guardian Technologies N7001V2 Panic Transmitter, Slimline Door/Window Transmitter, 1 5 W H Universal Transmitter, 26 Ð