Compatible Glass Break Detectors

Use detectors which are compatible with the following ratings:

Standby Voltage:..........5VDC-Ð13.8VDC

Standby Resistance:

Greater than 20k ohms (equivalent resistance of all detectors

 

in parallel)

Alarm Resistance:

Less than 1.1k ohms (see note below)

Alarm Current:

2 mA -Ð10 mA

Reset Time:

Less than 6 seconds

The IEI 735L series detectors have been tested and found to be compatible with these ratings. Up to 50 IEI 735L detectors, connected in parallel, may be used (the alarm current provided by this zone is sufficient to support operation of only one detector in alarmed state). Follow the manufacturer's recommendations on proper installation.

Detectors which exceed 1.1k ohms in alarm, but maintain a voltage drop in alarm of less than 3.8 volts can also be used.

Zones 2-8 Advisories

If latching type devices are installed on both zones 1 & 8, and these zones are assigned to different partitions, there is a possibility that, if both devices go into alarm at the same time, the resetting of one device could cause the loss of alarm memory in the other device.

Use of N.O. or N.C. contacts on the same zone may prevent proper glass break detector operation.

UL NOTE: 4-wire smoke detectors cannot be used in UL installations.

Hard-wired Zone 9

Applications

This zone is unsupervised and is suitable for monitoring fast-

 

acting glass break sensors or vibration sensors when pro-

 

grammed for fast response.

 

 

Response Type

Any type except fire (09), and types 20Ð22 (these are used

 

only for 5800 series wireless transmitters).

 

 

Response Time

Fast (10 msec) or slow (350 msec) response selected in field

 

*14.

 

 

Max. Zone Resistance

300 ohms

 

 

Unsupervised Usage

¥ Only closed circuit devices can be used.

 

¥ Connect these devices in series with one another between

 

terminals 22 & 23.

 

 

Zone 9 Advisories

Avoid using mechanical magnetic or relay type contacts in this zone when programmed for fast response.

UL NOTE: The interconnecting wires from zone 9 shall be no longer than 3 feet, with no intervening walls or barriers for UL installations.

Ð 19 Ð

Page 19
Image 19
Guardian Technologies VISTA-40, N7001V2 installation instructions Compatible Glass Break Detectors, 19 Ð