Contact ID Reporting

This is the only format that can identify all 64 protection zones by their unique

 

zone (Contact) ID numbers, and provides a 1-digit event qualifier and 3-digit,

 

specifically defined event code which quickly identifies the condition being

 

reported.

 

 

Contact ID reports in DTMF (Dual Tone Multi-Frequency @ 10 characters per

 

second) and responds to a 1400 Hz followed by 2300 Hz handshake, and a 1400

 

Hz kissoff. This format also uses checksum instead of two message verification. A

 

complete report takes under 3 seconds.

 

Contact ID Reporting takes the format: CCCC Q EEE GG ZZZ

 

where:

 

 

 

CCCC

=

Customer (subscriber) number.

 

Q

=

Event qualifier, where: E=new event (1) and R= restore (3)

 

EEE

=

Event code (3 hexadecimal digits), defined in the table below.

 

GG

=

Partition number.

ZZZ= Zone/contact ID number reporting the alarm (001-099), or user number (001-099) for open/close reports. System status messages (AC Loss, Walk Test, etc.) contain zeroes in the ZZZ location.

TABLE OF CONTACT ID EVENT CODES

Code

Definition

110

Fire Alarm

121

Duress

122

Silent Panic

123

Audible Panic

131

Perimeter Burglary

132

Interior Burglary

133

24 Hour Burglary (zone type 11 if supported)

134

Entry/Exit Burglary

135

Day/Night Burglary

150

24 Hour Auxiliary

301

AC Loss

302

Low System Battery

305

System Reset

306

Program Tamper

309

Battery Test Fail

332

Poll Loop Short-Trouble

333

Addressable Device Failure

373

Fire Loop Trouble

380

Trouble (global)

 

 

ADVISORY:

Code

Definition

381

Loss of Supervision - RF

382

Loss of RPM Supervision

383

RPM Sensor Tamper

384

RF Transmitter Low Battery

401

O/C By User

403

Power-Up Armed

406

Cancel by User

407

Remote Arm/Disarm (Download)

408

Quick Arm

409

Keyswitch O/C

411

Call back Requested

441

Armed STAY

570

Bypass

602

Periodic Test

606

Audio Alarm Verificationto follow (AAVÐlisten-in)

607

Walk Test Mode, 2-Way Audio Test

621

Event Log Reset

625

Time/Date Reset

626

Time/date inaccurate

 

 

Ademco's new Contact ID reporting is capable of uniquely reporting all 64 zones of information, as well as openings and closings for all 70 users, to central stations equipped with the Ademco 685 receiver using software level 4.4 or higher. Must be level 4.6 to fully support all new VISTA-40 report codes. 685 software levels below 4.4 cannot support Contact ID reporting. For information regarding updating the 685 receiver, contact the Technical Support group (see CONTACTING TECHNICAL SUPPORT section toward the end of this manual).

NOTE: Contact ID event code Ò606Ó is sent only if a VIM, and at least one 2-way voice keypad is used, and the AUTO CALLBACK option is disabled. If AUTO CALLBACK option is enabled, then the restriction that the 685 Rev number must be 4.6 or higher no longer applies, and the 2-way voice feature will work with ANY central station receiver.

Ð 73 Ð

Page 73
Image 73
Guardian Technologies VISTA-40, N7001V2 installation instructions Eee, Table of Contact ID Event Codes, 73 Ð