2-WIRE POLLING LOOP EXPANSION (Zones 10 through 64)

General Information

The following table summarizes polling loop expansion characteristics.

Applications

¥

Built-in 2- wire polling loop interface allows the number of

 

 

zones to be expanded from the basic 9 zones to up to 64

 

 

zones using various Remote Point Modules (RPMs). See

 

 

ADVISORIES below.

 

¥

The polling loop provides power to sensors and serves as

 

 

communication path between the panel and sensors.

 

¥

Refer to the list of compatible devices at the end of this

 

 

section.

RPM Address (ID)

¥

Each sensor must be assigned a unique address ID number

 

 

(from 10-64) before being connected to the polling loop. Care

 

 

must be taken to assign unique ID numbers to each sensor in

 

 

order to allow the panel to supervise and provide keypad

 

 

status indications for individual sensors.

 

¥

Most RPMs have DIP switches to set their addresses. The

 

 

4139SN, 4191SN, 4939SN, 4959SN and 998MX have

 

 

preprogrammed serial numbers which must be "enrolled" by

 

 

the control via the #93 menu programming mode.

 

 

 

Connections

¥

Connect RPM sensors to terminals 24 & 25.

 

¥

Sensors can be connected to a single run, or groups of

 

 

sensors may be connected to separate wire runs, star

 

 

configuration, without affecting the panel's ability to supervise

 

 

individual sensors.

 

¥

Follow the wiring instructions provided with individual

 

 

sensors. Be sure to observe sensor polarity when wiring.

 

¥

The maximum allowable wire run length between the panel

 

 

and the last sensor on a given wire run is shown in the table

 

 

below.

 

 

 

Maximum Polling Loop Wire Runs

 

 

Wire Gauge

Max. Length

 

 

 

#22 gauge

650

feet

 

Note: Twisted pair recommended

 

#20 gauge

950

feet

 

for all normal wire runs.

 

 

 

 

#18 gauge

1500

feet

 

 

 

#16 gauge

2400

feet

 

 

 

 

 

 

 

 

 

Important: When in a star configuration, no individual run can be longer than the table indicates, and the total length of all the sensor star runs, combined, cannot exceed 4000'. If using shielded wire, the maximum is 2000'. If longer wire runs are needed, a 4197/4297 Loop Extender Module must be used (see instructions included with the 4197/4297).

Intercom Interference

If an intercom system is being used, the polling loop wires must be as far from the intercom wiring as possible (minimum 6"). If this spacing cannot be achieved, shielded wire must be used. If this is not done, interference on the intercom system might occur. Also note that the maximum total wire length supported is cut in half when shielded wire is used.

NOTE: Shield must be terminated at control terminal 30.

Advisories

The maximum allowable current draw from the polling loop is 64mA. Refer to the POLLING LOOP CURRENT DRAW WORKSHEET (found in the POWERING THE SYSTEM section of this manual) for current draws of various polling loop devices.

Make certain to include the total current drawn on the polling loop in the AUXILIARY CURRENT DRAW WORKSHEET (see POWERING THE SYSTEM section) when figuring the total auxiliary load on the panel's power supply.

Ð 20 Ð

Page 20
Image 20
Guardian Technologies N7001V2, VISTA-40 Maximum Polling Loop Wire Runs Wire Gauge Max. Length, 20 Ð