Maintenance 113
Regularmaintenance of the battery module is an absolutenecessity. Periodic inspectionsof battery and terminal
voltages,specific gravity, and connectionresistance should be made. Strictly follow the proceduresoutlined in
the battery manufactu rer’s manual.
Valve-regulatedlead-acid (sealed-top)batteries do require periodic maintenance. Though theydo not require
maintenanceof electrolyte levels, battery voltageand connection resistance checks should be made.
Sinceindividual battery characteristicsare not identical, and may change over time, the UPS module is equipped
withcircuitry to equalize battery cell voltages. This circuitincreases charging voltage to maintain flooded type
battery cells at full capacity.
Theequalizing charge time period is adjustable from zero to 72 hours and can be initiatedautomatically or man-
ually.Refer to 3.0 - Operation.
NOTE
Donot use equalize charging with valve-regulatedlead-acid batteries.
Consultthe battery manufacturer's manual for specificinformation about equalize
charging.
Battery Voltage Record
Date
Float Voltage
(VoltsDC )
Nominal Voltage
(VoltsDC )
Ambient Temp.
(°F)
*___________ *______________________ *______________________ *______________________
___________ ______________________ ______________________ ______________________
___________ ______________________ ______________________ ______________________
___________ ______________________ ______________________ ______________________
___________ ______________________ ______________________ ______________________
___________ ______________________ ______________________ ______________________
___________ ______________________ ______________________ ______________________
___________ ______________________ ______________________ ______________________
___________ ______________________ ______________________ ______________________
___________ ______________________ ______________________ ______________________
___________ ______________________ ______________________ ______________________
___________ ______________________ ______________________ ______________________
___________ ______________________ ______________________ ______________________
*To be completed by Liebert Customer Service Representative at time of start-up.