54 Operation
Remote Monitor

TheRemote Monitor Panel (optional) displays eight(8) alarms. These alarms are also available for customer use

througha set of contacts on a separate terminal board.

Whenthe New Alarm, System Summary Alarm, or ModuleSummary Alarm is activated, you can getmore

informationat the Operator Display Panel or through a remote terminal. Refer to 3.1.14 - Communication

Interfaces.

.

Thefollowing alarms, as well as those listed above, willactivate the System Summary Alarm or the Module

Summary Alarm.

SCC and Module Remote Monitor Indications
SCC Remote Monitor Indications Channel Module Remote Monitor Indications
LoadOn UPS CH1 OutputCB Open
LoadOn Bypass CH2 BatteryCB Open
BatteryDischarging CH3 BatteryDischarging
LowBattery Warning CH4 LowBattery Warning
Overload CH5 ControlFailure
AmbientOver-Temp CH6 AmbientOver-Temp
SystemSummary Alarm CH7 ModuleSummary Alarm
NewAlarm CH8 New Alarm
Other Alarms That Activate Summary Alarms
Other Alarms That Activate
SystemSummary Alarm
Other Alarms That Activate
Module Summary Alarm
ControlPower Fail BlowerFailed
EmergencyOff ControlPower Fail
ModuleSummary Alarm DCCapacitorFuse Blown
OutputOver/Under Frequency DC Ground Fault
OutputOver-Voltage DC Over-VoltageShutdown
OutputUnder-Voltage EmergencyOff
OverloadTransfer Equipment Over-Temperature
StaticSwitch Unable Inverter Fault
LowBattery Shutdown
Overload
OverloadShutdown
RectifierFuse Blown
ReversePower