
Figure 9 System Control Cabinet Operator Controls (SCCB Pictured)
Item  | Description | Function  | 
1  | UPS Output Circuit  | This motorized circuit breaker connects the critical load to the UPS system output.  | 
  | Breaker  | 
  | 
2  | System Bypass Circuit  | This motorized circuit breaker connects the critical load to the bypass line.  | 
  | Breaker  | 
  | 
3  | Operator Control Panel  | Refer to Figure 10 for controls available on this panel.  | 
  | 
  | 
  | 
4  | Interlock Button  | Refer to Figure 11.  | 
  | (on rear of Control Panel)  | 
  | 
5  | Close Bypass Switch  | Refer to Figure 11.  | 
  | (behind door)  | 
  | 
6  | Bypass Reset Switch  | Refer to Figure 11.  | 
  | (behind door)  | 
  | 
7  | Static Switch Disconnects  | These manually operated switches disconnect the static switch from the bypass  | 
  | (behind door)  | line and from the critical load. They are normally ON (closed). Turn them OFF  | 
  | 
  | (open) only to isolate (disconnect) the static switch for maintenance procedures.  | 
8  | Reset Switches (SW1) for  | Press these two switches before closing Static Switch Disconnects when  | 
  | Static Switch Disconnects  | recovering from a shutdown that includes loss of Control Power. Green LED on  | 
  | (behind door)  | means Control Power is available. Red LED on means Reset Switch needs to be  | 
  | 
  | pushed.  | 
9  | Control Power Disconnect  | Normally ON. Turn OFF Control Power only when required for maintenance  | 
  | (behind door)  | procedures.  | 
Operation 25