Figure 11 Switches Behind SCC Control Panel Door

Item

Description (Location)

Function

1

Interlock Button

Press this button to make authorized changes to any site parameter protected by

 

(on rear of Control Panel)

the Security Access function. These include the time, date, auto-dial phone

 

 

number, and other site parameters.

2

Bypass Reset Switch

Press this button to reset the transfer relays during start-up, after an Emergency

 

(SW1, on Transfer

Power Off shutdown. You must press this button before the Close Bypass Switch

 

Relay Board)

(Item 3).

3

Close Bypass Switch

Press this button to close the Bypass circuit breaker during a start-up procedure, if

 

(SW1, on System

it remains open after a shutdown procedure (refer to 3.3.1 - Start-Up Procedure).

 

Interface Board)

Note that the Static Switch Disconnects must be OFF to reset the Bypass circuit

 

 

breaker. See also Bypass Reset Switch (Item 2).