Table 1

 

Alarm Messages - Meaning and Corrective Action

Alarm

 

Cabinet

Special

Meaning and

Message

 

Location

Functions

Corrective Action in Brackets [ ]

AC INPUT

 

 

 

 

Input Fail

 

MMU

The rectifier input line voltage is outside of specified limits or the

 

 

 

 

input circuit breaker is opened while the battery circuit breaker

 

 

 

 

remains closed. The battery supplies power to the critical load

 

 

 

 

through the UPS inverter.

DC BUS

 

 

 

 

DC Ground Fault

 

MMU

L, S

Either the positive (+) or negative (-) DC bus is grounded. No transfer

 

 

 

 

or shutdown occurs.

 

 

 

 

[Contact Liebert Global Services at once. Do not attempt to locate or

 

 

 

 

repair the fault.]

DC Capacitor

 

MMU

D, F, S

At least one DC capacitor fuse has opened. The UPS module is

Fuse Blown

 

 

 

taken off-line and the input and battery circuit breakers trip open.

 

 

 

 

[Contact Liebert Global Services at once. Do not attempt to reset the

 

 

 

 

circuit breakers.]

Battery CB Open

 

MMU

R, S

The module battery circuit breaker (MBD) is open. This circuit

 

 

 

 

breaker can be opened either manually or automatically in a UPS

 

 

 

 

shutdown procedure. If the UPS is operating with this breaker open,

 

 

 

 

the critical load is not protected from loss of the utility source

 

 

 

 

power.

 

 

 

 

[After AC power is restored and the DC bus is at 100% operating

 

 

 

 

voltage, manually close the battery circuit breaker so the rectifier can

 

 

 

 

charge the battery.]

Battery

 

MMU

R, S

The battery is discharging. This occurs whenever the battery

Discharging

 

 

 

supplies power to the load for more than 5 seconds because of input

 

 

 

 

power failure, a rectifier problem, or an overload condition. If the

 

 

 

 

input power or a source of auxiliary power is restored to the UPS

 

 

 

 

module, the UPS automatically returns to normal operation.

 

 

 

 

[Watch the battery voltage carefully. Reduce the load (begin

 

 

 

 

controlled shutdown) to extend the battery back-up time. Reset the

 

 

 

 

UPS alarms after the input power is restored. The message clears

 

 

 

 

after 30 seconds.]

Low Battery

 

MMU

R, S

The battery voltage is approaching the minimum discharge voltage

Warning

 

 

 

(approximately 5 minutes remaining).

 

 

 

 

[Complete the controlled shutdown of the critical load. Reset the

 

 

 

 

alarms if the input power is restored before shutdown.]

Low Battery

 

MMU

D, F, L, S

The battery voltage has decreased to the minimum discharge value.

Shutdown

 

 

 

The UPS module is taken off-line (no power to the critical load)

 

 

 

 

and the battery and input circuit breakers trip open.

 

 

 

 

[Perform a UPS system start-up procedure when AC power

 

 

 

 

becomes available.]

DC Over-Voltage

 

MMU

D, F, L, S

The maximum preset value of the DC Bus voltage has been

Shutdown

 

 

 

exceeded. The UPS module is taken off-line and the input and

 

 

 

 

battery circuit breakers trip open.

 

 

 

 

[Contact Liebert Global Services at once. A fault may have occurred

 

 

 

 

within the UPS. Do not attempt to reset the circuit breaker.]

BYPASS

 

 

 

 

Load On Bypass

 

SCC

D, E, F

The critical load is being supplied power from the bypass line, and is

 

 

 

 

therefore exposed to utility power disturbances.

 

 

 

 

[Clear all of the alarms before attempting to retransfer the load from

 

 

 

 

the bypass line to the UPS.]

Table 1 Abbreviations

 

 

D = auto-dial;

L = latches

 

 

E = reports only;

R = remote

 

 

F = freezes;

S = summary

 

 

D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs

D# = auto-dial initiated through Module N (1-6) off-line

70

Operation

DISCONTINUED

 

 

PRODUCT

Page 76
Image 76
Liebert Series 600T Input Fail, DC Ground Fault, DC Capacitor, Fuse Blown, Battery CB Open, Power, Discharging, Shutdown