Alarm Messages - Meaning and Corrective Action (continued)

Alarm

 

Cabinet

Special

Meaning and

Message

 

Location

Functions

Corrective Action in Brackets [ ]

BYPASS (Contʼd.)

 

 

 

Auto Transfer to

 

SCC

D, E, F

The critical load has been automatically transferred to the bypass

Bypass

 

 

 

line.

 

 

 

 

[Use the History Status screen to determine the cause for the

 

 

 

 

transfer. Clear all of the alarms before attempting to retransfer the

 

 

 

 

load from bypass to UPS.]

Auto Retransfer

 

SCC

An automatic retransfer will be initiated when the OK to Transfer

Primed

 

 

 

condition has been present for 10 seconds, if the overload has

 

 

 

 

dropped below 100% of the rated SCC current and if enough UPS

 

 

 

 

modules are on-line.

Manual Reset/

 

SCC

A manual retransfer is required. Either a system overload condition

Retransfer

 

 

 

has lasted more than 5 minutes, or no more auto-retransfer attempts

 

 

 

 

are available. Note that this alarm is only used if auto-retransfer

 

 

 

 

attempts are enabled.

 

 

 

 

[Perform a manual retransfer if all necessary conditions are present.]

Static Switch

 

SCC

S

The UPS output is not synchronized to the bypass power source.

Unable

 

 

 

The static bypass switch is disconnected, or it has failed internally.

 

 

 

 

[Emergency and overload transfer to the bypass source is not

 

 

 

 

available. Manually set the Static Switch Disconnects to ON (closed)

 

 

 

 

if the static switch is disconnected. If the alarm conditions are

 

 

 

 

automatically corrected, reset the alarm to clear it. Contact Liebert

 

 

 

 

Global Services if the alarm stays on.]

Bypass Not

 

SCC

The bypass power source voltage is not within specifications.

Available

 

 

 

[Check the bypass power source.]

Bypass Phase

 

SCC

The power conductors on the bypass line are not wired to the UPS in

Sequence Wrong

 

 

the required sequence. This alarm should appear only during initial

 

 

 

 

start-up or after a repair to the source power system.

 

 

 

 

[Disconnect power from the bypass line and correct the wiring. A

 

 

 

 

Liebert Global Services representative must be present during initial

 

 

 

 

start-up of your UPS System.]

UPS SYSTEM

 

 

 

 

Input Current

 

MMU

E

At least one input phase differs from the average current by 10% or

Unbalanced

 

 

 

more for four (4) hours. Contact Liebert Global Services. If the

 

 

 

 

condition persists, transfer the load to the bypass line.

Control Power

 

SCC

L, S

The logic control power supply from the UPS output is not operating

Fail

 

MMU

L, R, S

properly. The UPS module continues operating but will shut down if

 

 

 

 

the input power fails. The SCC continues operating but will shut

 

 

 

 

down if the bypass power fails. Contact Liebert Global Services

 

 

 

 

immediately.

Output Over/

 

SCC

L, S

Output frequency differs from the nominal (60 Hz) by more than 0.5

Under Frequency

 

 

Hz. No transfer or shutdown occurs.

 

 

 

 

[Contact Liebert Global Services at once.]

Output Under-

 

SCC

D, F, L, S

The UPS system output voltage is under the minimum (-12%)

Voltage

 

 

 

deviation from nominal. The load automatically transfers to the

 

 

 

 

bypass line.

 

 

 

 

[If the alarm condition is no longer present, reset the alarm and

 

 

 

 

retransfer the load from bypass to UPS. Contact Liebert Global

 

 

 

 

Services if alarm persists.]

Output Over-

 

SCC

D, F, L, S

The UPS system output voltage is above the maximum (+10%)

Voltage

 

 

 

deviation from nominal. The load automatically transfers to the

 

 

 

 

bypass line. All UPS modules are taken off-line and are shut down.

 

 

 

 

[Contact Liebert Global Services at once. Do not attempt to reset

 

 

 

 

circuit breakers.]

Table 1 Abbreviations

 

 

D = auto-dial;

L = latches

 

 

E = reports only;

R = remote

 

 

F = freezes;

S = summary

 

 

D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs

D# = auto-dial initiated through Module N (1-6) off-line

Operation 71