3.1.2Monitor/Mimic Display Screen

From SCC Master Menu move the highlighted cursor to MONITOR/MIMIC DISPLAY. Press the Select pad and the Monitor/Mimic screen is displayed.

The Monitor/Mimic display screen is a simplified block diagram of the UPS system. This screen gives the oper- ator an overall view of the power flow through the UPS system. The screen consists of three major sections: the input/UPS metering section, the load metering section, and the status and alarm message areas. The metered parameter values on the Monitor/Mimic screen are updated at one-second intervals.

Figure 14 SCC Monitor/Mimic Display Screen

BYPASS INPUT A-B B-C C-A 480V 480V 480V

60.0 Hz

UPS INPUT PWR A-B B-C C-A 480V 480V 480V

1

2

UPS RATINGS

SCCB 1600

OUTPUT VOLTAGE A-B B-C C-A 480V 480V 480V

4

3

LOAD

627 KVA / 502 KW

A B C 755A 755A 755A

3 OF 3 MODULES

CONNECTED REDUNDANT

5

MOD 1 ON LINE

MOD 2 ON LINE

MOD 3 ON LINE

60.0 Hz

OK to Transfer

Static Switch Connected

6 7

Input Metering Displays

NOTE

All voltage readings are phase-to-phase measurements (A-B, B-C, and C-A). All current readings are phase measurements (A, B, and C).

Item 1 - Bypass Input. This block displays the bypass input voltage and the bypass input frequency. The System Bypass Breaker is shown to the right of this block. The status of the circuit breaker is illustrated as open or closed.

Item 2 - UPS Input Pwr. This block displays the input voltage to the UPS modules.

Output Metering Displays

Item 3 - UPS Ratings. The SCC current rating is specified at the top of this block. The UPS system output volt- age and frequency are also displayed in this block. The UPS Output Breaker is shown to the right of this block. The status of the circuit breaker is illustrated as open or closed.

Item 4 - Load. This block displays the total output power to the critical load in kVA and kW. The critical load current per phase is also displayed in this block. Note that kW is not displayed when the load is on the bypass line.

The load block also indicates the number of modules connected and whether the UPS system is operating in the redundant or non-redundant mode.

During an overload condition, the time remaining before shutdown or transfer is displayed at the bottom of the load box.

Operation 31