Table 1

 

Alarm Messages - Meaning and Corrective Action (continued)

Alarm

 

Cabinet

Special

Meaning and

Message

 

Location

Functions

Corrective Action in Brackets [ ]

UPS SYSTEM (Contʼd.)

 

 

Overload

 

SCC

R, S

The UPS output current exceeds the rated system load current. This

 

 

MMU

S

condition causes an alarm only, the UPS does not shut down.

 

 

 

 

[Determine cause of the overload. Reduce the load until the overload

 

 

 

 

condition is corrected. Reset the UPS alarm.]

Overload Transfer

SCC

D, F, L, S

The load on the UPS has exceeded the current versus time window

 

 

 

 

of system overload capacity. The UPS system transfers the load to

 

 

 

 

bypass.

 

 

 

 

[Reduce the load. If the system does not initiate an automatic load

 

 

 

 

retransfer, manually retransfer the critical load from the bypass line

 

 

 

 

to the UPS. Reset the alarm.]

Module Summary

SCC

S

An alarm message (see lists in SCC and Module Remote Monitor

Alarm

 

 

R (MMU)

Indications and Other Alarms That Activate Summary Alarms in

 

 

 

 

3.1.5 - System Configuration Screens) or the watchdog timer has

 

 

 

 

activated the Module Summary Alarm.

 

 

 

 

[Clear alarm conditions, if possible.]

Module N Off Line

SCC

D

The output circuit breaker of Module N is open. The number N will

 

 

 

R (MMU)

identify the module (1 through 6).

 

 

 

 

[Review active alarms at Module N and clear alarm conditions, if

 

 

 

 

possible.]

Inverter

 

MMU

Inverter output is not synchronized with the UPS system critical bus.

Nonsynchronized

 

 

This also means the output circuit breaker is open and should not be

 

 

 

 

closed until the output is in sync. This condition may correct itself. If

 

 

 

 

not, shut down the UPS module and then perform a start-up

 

 

 

 

procedure.

 

 

 

 

[Contact Liebert Global Services if condition persists.]

Overload

 

MMU

D, F, L, S

The UPS output current has exceeded 175% of the rated full load or

Shutdown

 

 

 

the overload capacity has been exceeded. The UPS module is taken

 

 

 

 

off-line and shut down.

 

 

 

 

[Contact Liebert Global Services at once. Do not attempt to reset

 

 

 

 

circuit breakers.]

Reverse Power

 

MMU

D, F, L, S

Excessive reverse power flow from the critical bus into the UPS

 

 

 

 

inverter has occurred, probably because of low inverter output

 

 

 

 

voltage or a phase mismatch. The UPS module is taken off-line and

 

 

 

 

is shut down.

 

 

 

 

[Contact Liebert Global Services immediately. Do not attempt to

 

 

 

 

reset circuit breakers.]

Inverter Fault

 

MMU

D, F, S

At least one of the fuses has opened or an inverter fault was

 

 

 

 

detected. The UPS module is taken off-line and is shut down.

 

 

 

 

[Contact Liebert Global Services immediately. Do not attempt to

 

 

 

 

reset the circuit breakers.]

Communication

 

SCC

S

The COM FAIL status message is as important as an alarm

Failure

 

 

 

message. Refer to 3.1.13 - Alarm and Status Messages.

Battery Cycle

 

D, E

The optional Battery Cycle Monitor can retain information about the

Buffer Warning

 

 

 

last 132 battery discharge events. When the storage buffer

 

 

 

 

approaches its capacity, this warning message is broadcast via

 

 

 

 

terminal and modem communication channels, and a complete

 

 

 

 

listing of all records is sent to the terminal port. The message clears

 

 

 

 

after 30 seconds.

Table 1 Abbreviations

 

 

 

D = auto-dial;

L = latches

 

 

E = reports only;

R = remote

 

 

F = freezes;

S = summary

 

 

D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs

D# = auto-dial initiated through Module N (1-6) off-line

72

Operation

DISCONTINUED

 

 

PRODUCT

Page 78
Image 78
Liebert Series 600T manual Overload Transfer, Module Summary, Indications and Other Alarms That Activate Summary Alarms