82 Operation
3.2.4 Input Power Failure( LoadOn Battery)
Ifthe utility AC power source fails, or is outside the acceptablerange, the battery plant becomes the power
sourcefor the UPS module inverters. The UPS system continues to supplypower to the critical load, and also to
thecontrols of the UPS modules and the SCC.
Youcan use the Battery Timescreen at the UPS modules to monitor thepresent battery voltage compared to the
shutdownvalue. The length of time the battery can sustain the load dependson the size of the load and the size
andcondition of the battery plant. The battery plant is usually largeenough to supply a 100% rated load for 15
minutes.
Alarmmessages that indicate battery status are Battery Discharge,Low Battery, and Battery Shutdown. The
voltagelimits for these alarmsare displayed on the UPS module Alarm LimitSettings screen. These limits were
selectedfor your installation by Liebert Global Servicesduring initial start-up.
Thebattery block in the UPS module Monitor/Mimic Display indicatesCharge or Discharge and the current in
Amperes.Maximum battery discharge current ranges from 324 amps (for 150 kVA)to 1620 amps (for 750
kVA).Refer to the separate InstallationManual or drawings for specific data on your system.
Figure 51 Input Power Fail (Load on Battery)
BIB
SKRU
MIB
MBB
#2UPS
CB1
#1UPS
CB1
System
Controls
#3UPS
CB1
RIB RIB RIB BFB
Output
SBB
SBS
I
CB2
II
CB2 CB2
R RR
SCCT
SCCT
(canaccommodate up t o 6UP S modules)
ToCriticalLoad
Battery
MBD
Battery
MBD
Battery
MBD