The alarm conditions that cause the History Status buffer to stop gathering new data are:

SCC

Module

Auto Transfer to Bypass

DC Cap Fuse Blown

Output Over-Voltage

DC Over-Voltage Shutdown

Output Under-Voltage

Inverter Fault

Overload Transfer

Low Battery Shutdown

 

Overload Shutdown

 

Over-Temperature Timeout

 

Rectifier Fuse Blown

 

Reverse Power

Note that the Emergency Off alarm will also freeze the SCC History Status buffer with the Auto Transfer to Bypass alarm (if the load is on the UPS system when the alarm condition occurs).

The History Status buffer does not resume collecting new frames until the fault is cleared and the Alarm Reset pad is pressed for 15 seconds (or until the screen clears).

Operation 45