Operation 45
Thealarm conditions that cause the History Status bufferto stop gathering new data are:
Notethat the Emergency Off alarm will also freeze the SCC HistoryStatus buffer with the Auto Transfer to
Bypassalarm (if the load is on the UPS system when the alarm condition occurs).
TheHistory Status buffer does not resume collecting new frames untilthe fault is cleared and the Alarm Reset
padis pressed for 15 seconds (or until the screen clears).
SCC Module
AutoTransfer to Bypass DC Cap Fuse Blown
OutputOver-Voltage DC Over-VoltageShutdown
OutputUnder-Voltage InverterFault
OverloadTransfer Low BatteryShutdown
OverloadShutdown
Over-TemperatureTimeout
RectifierFuse Blown
ReversePower
DISCONTINUED
PROD U C T