118 Specificationsand Ratings
5.2 EnvironmentalConditions
Enclosure: The UPSis housed in a NEMA-1 enclosure. The enclosureis
designedfor indoor use only and is not to be subjected to falling
objectsor precipitation.
Recommended Operating
Temperature:
25°C
Maximum Operating Temperature: 40°C(design temperature) without derating
Minimum Operating Temperature: 0°C
Storage Temperature: -20°Cto 70°C
Typical Battery Temperature
Requirements:
Averageannual temperature shall not exceed 27°C. Peak
temperatureshall not exceed 43°C during any 24-hour period. See
batterymanufacturerʼs recommendations.
Relative Humidity: 0to 95% without condensation
Operating Elevation: Sealevel to 1219 meters (4000 ft.) without derating
Storage Elevation: Sealevel to 12,192 meters (40,000 ft.)
Audible Noise: 69dBA typical, measured 5 feet from unit
Derating for Higher Ambient
Temperatures:
91%at 45°C
82%at 50°C
73%at 55°C
Consultyour Liebert sales representative regarding applicationsin
highambient temperatures. Special temperature sensorsmust be
installedat the factory.
Derating for Higher Elevations: 95%at 2000 meters
94%at 2200 meters
93%at 2400 meters
92%at 2600 meters
91%at 2800 meters
90%at 3000 meters
NOTE
Thiscategory of electronicequipment is agency rated for use inan atmosphere free of
conductiveparticles. Some industrial facilitiesmay require a room air filtration
systemto keep the UPS free of excess moisture and contaminants.
TheUPS system is designed to operate continuously at 40°C. However,design
equipmentlife expectancy will be extended with lowertemperatures (25°C is
recommended).