5.2

Environmental Conditions

 

 

 

 

 

Enclosure:

The UPS is housed in a NEMA-1 enclosure. The enclosure is

 

 

designed for indoor use only and is not to be subjected to falling

 

 

objects or precipitation.

 

Recommended Operating

25°C

 

Temperature:

 

 

Maximum Operating Temperature:

40°C (design temperature) without derating

 

Minimum Operating Temperature:

0°C

 

Storage Temperature:

-20°C to 70°C

 

Typical Battery Temperature

Average annual temperature shall not exceed 27°C. Peak

 

Requirements:

temperature shall not exceed 43°C during any 24-hour period. See

 

 

battery manufacturerʼs recommendations.

 

Relative Humidity:

0 to 95% without condensation

 

Operating Elevation:

Sea level to 1219 meters (4000 ft.) without derating

 

Storage Elevation:

Sea level to 12,192 meters (40,000 ft.)

 

Audible Noise:

69 dBA typical, measured 5 feet from unit

 

Derating for Higher Ambient

91% at 45°C

 

Temperatures:

 

 

82% at 50°C

 

 

 

 

73% at 55°C

 

 

Consult your Liebert sales representative regarding applications in

 

 

high ambient temperatures. Special temperature sensors must be

 

 

installed at the factory.

 

Derating for Higher Elevations:

95% at 2000 meters

 

 

94% at 2200 meters

 

 

93% at 2400 meters

 

 

92% at 2600 meters

 

 

91% at 2800 meters

 

 

90% at 3000 meters

NOTE

This category of electronic equipment is agency rated for use in an atmosphere free of conductive particles. Some industrial facilities may require a room air filtration system to keep the UPS free of excess moisture and contaminants.

The UPS system is designed to operate continuously at 40°C. However, design equipment life expectancy will be extended with lower temperatures (25°C is recommended).

118

Specifications and Ratings

DISCONTINUED

 

 

PRODUCT

Page 124
Image 124
Liebert Series 600T manual Environmental Conditions