Separate / Simultaneous Outputs

The RS-232 interface can support a modem plus either a local terminal or a local monitor. Likewise, the SiteScan port can support either SiteScan or SNMP communications. Whatever interfaces you use will all operate simulta- neously.

Table 3 Series 600T Terminal Commands

Key(s)

Function

A, return

Displays Present Status Report screen. NOTE: For all three report screens, a

AN (N=1 to 6), return

number 1 through six in place of N will access an individual UPS module. If no

 

number is entered, you will get a report from the SCC.

^B (control-B), return

Displays Event History Report screen, starting with the most recent frame and then

^BN (N=1 to 6) return

scrolling back through earlier frames.

C, return

Displays History Status Report screen starting with the most recent frame and then

^CN (N=1 to 6), return

scrolling back through the earlier frames.

F (no return)

Freezes data output. This stops the data scrolling on the monitor to allow closer

 

study or a printout. This is a toggle switch command. Press the F key again to

 

resume data scrolling.

G, return

Resets (unfreezes and clears) the History Status Report memory buffer. This erases

 

the alarm messages and meter indications that were stored immediately before and

 

after a significant system fault. NOTE: Do not reset the History Status Report

 

memory buffer until operation and maintenance personnel have reviewed it as a

 

troubleshooting tool.

Q (no return)

The data output stops (quits). The UPS communication system remains on stand-

 

by, ready to receive the next communication command. NOTE: To return to the

 

beginning of the Event History or History Status Report, press Q, then request your

 

desired report again.

d mm/dd/yy, return

This entry sets the date (month/day/year) in the UPS system clock. You must

 

include the slash (/) as you key in the date. Note that the d command must be lower

 

case.

t hh:mm:ss, return

This entry sets the time (hour:minute:second) in the UPS system clock. You must

 

include the colon (:) as you key in the time. Note that the t command must be lower

 

case.

H, Return

Prompts the UPS system to hang up its modem (only applicable to the modem

 

communications port).

I, Return

Display Battery Cycle Monitor information for 0-30 second discharge events.

 

 

J, Return

Display Battery Cycle Monitor information for 31-90 second discharge events.

 

 

K, Return

Display Battery Cycle Monitor information for 91-240 second discharge events.

 

 

L, Return

Display Battery Cycle Monitor information for over 240 second discharge events.

 

 

M, Return

Display Status Summary screen of battery discharge events.

 

 

N, Return

Show detail information on all battery discharge events in order of occurrence

 

(Last-In, First-Out).

backspace

Moves cursor left to cancel previous entry or command.

 

 

Operation 77