Table 4

Torque Specifications (Unless Otherwise Labeled)

 

 

 

 

 

 

Nut and Bolt Combinations

 

 

 

 

 

 

Bolt

 

Grade 2

 

Electrical Connections

 

 

 

Standard

 

with Belleville Washers

 

 

Shaft

 

 

 

 

Size

 

Lb-in

N-m

 

Lb-in

 

N-m

 

 

1/4

 

53

6.0

 

46

 

5.2

 

 

5/16

 

107

12

 

60

 

6.8

 

 

3/8

 

192

22

 

95

 

11

 

 

1/2

 

428

48

 

256

 

29

 

 

 

 

 

 

 

 

 

 

 

Circuit Breakers With Compression Lugs

Terminal Block Compression Lugs

 

 

(For Power Wiring)

 

 

(For Control Wiring)

 

Current

 

 

 

 

 

AWG Wire

 

 

 

 

 

 

Lb-in

 

N-m

Size or

 

Lb-in

 

N-m

Rating

 

 

 

Range

 

 

400 - 1200

 

300

 

34

#22 - #14

 

3.5 to 5.3

 

0.4 to 0.6

Amps

 

 

 

 

 

 

 

 

 

 

4.4Detection of Trouble

There is no practical way to anticipate an impending malfunction. It is important that the operator check the instrument readings if abnormal equipment performance is suspected.

Items to check include:

1.Output voltage of all phases should be within 2% of normal voltage. Output currents on each phase should not normally differ by more than 20%. If a greater difference is noted, the load is unbalanced and corrective action should be taken to redistribute the load, if possible.

2.If the UPS has not operated on battery power during the last 10 hours, the batteries should require little charging current. Battery mimic should indicate normal DC voltage with the battery charge current no more than 31 Amperes.

3.Input current on each phase should be within 10% of the average input current.

4.Alarm messages indicate malfunction or impending malfunction. A daily check of the Operator Control Panel will help to provide an early detection of problems. Refer to Table 1 and Table 2 in 3.0 - Operation to interpret alarm messages.

5.Tracing a problem to a particular section is facilitated by alarm messages and the metered parameter indications. These are stored in the Status Reports and can be displayed at the Operator Control Panel or at an optional terminal. The Liebert Customer Service Engineer will also be familiar with test points inside the unit.

NOTE

If the UPS system has a blown fuse, the cause should be determined before you replace the fuse. Contact Liebert Global Services.

Maintenance 115

DISCONTINUED

PRODUCT

Page 121
Image 121
Liebert Series 600T manual Detection of Trouble, Torque Specifications Unless Otherwise Labeled