Table 4 | Torque Specifications (Unless Otherwise Labeled) |
| ||||||||
|
|
|
|
| Nut and Bolt Combinations |
|
|
|
| |
|
| Bolt |
| Grade 2 |
| Electrical Connections | ||||
|
|
| Standard |
| with Belleville Washers | |||||
|
| Shaft |
|
| ||||||
|
| Size |
|
|
| |||||
|
| 1/4 |
| 53 | 6.0 |
| 46 |
| 5.2 | |
|
| 5/16 |
| 107 | 12 |
| 60 |
| 6.8 | |
|
| 3/8 |
| 192 | 22 |
| 95 |
| 11 | |
|
| 1/2 |
| 428 | 48 |
| 256 |
| 29 | |
|
|
|
|
|
|
|
|
|
|
|
Circuit Breakers With Compression Lugs | Terminal Block Compression Lugs | |||||||||
|
| (For Power Wiring) |
|
| (For Control Wiring) |
| ||||
Current |
|
|
|
|
| AWG Wire |
|
|
|
|
|
|
| Size or |
|
| |||||
Rating |
|
|
| Range |
|
| ||||
400 - 1200 |
| 300 |
| 34 | #22 - #14 |
| 3.5 to 5.3 |
| 0.4 to 0.6 | |
Amps |
|
|
|
|
|
|
|
|
|
|
4.4Detection of Trouble
There is no practical way to anticipate an impending malfunction. It is important that the operator check the instrument readings if abnormal equipment performance is suspected.
Items to check include:
1.Output voltage of all phases should be within 2% of normal voltage. Output currents on each phase should not normally differ by more than 20%. If a greater difference is noted, the load is unbalanced and corrective action should be taken to redistribute the load, if possible.
2.If the UPS has not operated on battery power during the last 10 hours, the batteries should require little charging current. Battery mimic should indicate normal DC voltage with the battery charge current no more than 31 Amperes.
3.Input current on each phase should be within 10% of the average input current.
4.Alarm messages indicate malfunction or impending malfunction. A daily check of the Operator Control Panel will help to provide an early detection of problems. Refer to Table 1 and Table 2 in 3.0 - Operation to interpret alarm messages.
5.Tracing a problem to a particular section is facilitated by alarm messages and the metered parameter indications. These are stored in the Status Reports and can be displayed at the Operator Control Panel or at an optional terminal. The Liebert Customer Service Engineer will also be familiar with test points inside the unit.
NOTE
If the UPS system has a blown fuse, the cause should be determined before you replace the fuse. Contact Liebert Global Services.
Maintenance 115