Present Status

The Present Status screen shows the current status of the UPS system (SCC) or module. This screen displays any alarm messages that are present and the values of the metered parameters for each cabinet. Battery values are dis- played only at the UPS modules.

Each update sequence (every 4 milliseconds) is called a frame. The frame number is displayed in the upper right corner. The Present Status screen display is updated every two seconds.

Battery Time Remaining (in minutes) is displayed on the module screens during a battery discharge. The value is on the Battery Volts line in the TIME column (far right side of the screen). For the first two minutes of discharge, the Rated Time Remaining is displayed. After that, the Calculated Time Remaining is displayed, and updated every six seconds.

All the information on this screen, including Battery Time Remaining, is available to a local terminal or modem through the communications ports provided in the Series 600T UPS. Refer to Table 3 in this manual for key- board commands to use with the communication ports.

Figure 23 Present Status Report Screens, SCC (above) and Module

PRESENT STATUS

 

MODULE-0

01/12/98

14:06:26

FRAME 35

 

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

 

 

 

 

 

**** ACTIVE ALARMS ****

Batt Discharging

 

 

 

 

 

 

 

 

OUTPUT VOLTS

 

A

B

C

DC

LOAD

HERTZ

TIME

 

 

480

480

480

 

 

 

 

 

 

 

 

OUTPUT AMPS

 

325

325

325

 

 

 

60.0

 

 

 

OUTPUT FREQUENCY

 

 

 

 

270

0:06

 

 

LOAD KVA

 

0

0

0

 

 

 

 

 

BYPASS VOLTS

 

 

 

 

 

 

 

 

 

END OF REPORT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SELECT : EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESENT STATUS

 

MODULE-0

01/12/98

14:06:26

FRAME 35

 

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

 

 

 

 

 

**** ACTIVE ALARMS **** Batt Discharging

 

 

 

 

 

 

 

 

OUTPUT VOLTS

 

A

B

C

DC

LOAD

HERTZ

TIME

 

 

480

480

480

 

 

 

 

 

 

 

OUTPUT AMPS

 

325

325

325

 

 

60.0

 

 

 

OUTPUT FREQUENCY

 

 

 

480

 

 

0:09

 

 

BATTERY VOLTS

 

 

 

 

 

 

 

 

 

 

BATTERY AMPS

 

0

0

0

-645

 

 

 

 

 

 

 

INPUT VOLTS

 

 

 

 

 

 

 

 

 

INPUT AMPS

 

0

0

0

 

270

 

 

 

 

 

LOAD KVA

 

 

 

 

 

 

 

 

 

 

END OF REPORT

SELECT : EXIT

42